Amana PTAC Air Conditioner Error Codes

CODE: FP.
RESULT: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
FIX: No Action required. This setting will disengage when the room temperature rises above 43°F.

CODE: Fd.
RESULT: Front Desk switch is closed. All outputs are switched off.
FIX: Open front desk switch to allow occupant unit operation.

CODE: Eo.
RESULT: Un-Configured Service Board - All operation held awaiting configuration.
FIX: Enter Configuration Menu and set "C3" to "C" for coolers with electric heat or "H" for heat pumps.

CODE: EH.
RESULT: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
FIX: Open front emergency hydronic switch to allow occupant unit operation.

CODE: LS.
RESULT: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
FIX: Open load shedding switch to allow occupant unit operation.

CODE: On.
RESULT: Control is configured to respond to a wired thermostat.
FIX: No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

CODE: oP.
RESULT: Open Door Lockout (DS1 & DS2 open; wireless).
FIX: Close Room Door. Unit will not condition space with door open.

CODE: nP.
RESULT: Window Switch Lockout - (LS & INN open).
FIX: Close Room Door or Window. Unit will not condition space with door or window open.

CODE: HP.
RESULT: Heat Sentinel - (WIAT > u3).
FIX: No action required. This setting will disengage when the room temperature falls.

CODE: Ur.
RESULT: Un-Rented Status (EHH & INN or wireless).
FIX: Front Desk needs to set to Rented mode (if applicable).

CODE: F1.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

CODE: F2.
RESULT: Wireless Remote Thermostat failure.
FIX: Replace Wireless Thermostat.

CODE: F3.
RESULT: Indoor Ambient Thermistor reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor.

CODE: F4.
RESULT: Indoor Coil Thermistor either above or below operating tolerances.
FIX: Replace Red Indoor Coil Thermistor.

CODE: F5.
RESULT: Wireless Thermostat failure.
FIX: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

CODE: F6.
RESULT: Indoor Discharge Thermistor either above or below operating tolerances.
FIX: Replace Yellow Indoor Discharge Thermistor.

CODE: Fb.
RESULT: Low Remote Battery Warning.
FIX: Replace Batteries in Wireless Devices.

CODE: H1.
RESULT: High Voltage Protection engaged. Power supply voltage is to high.
FIX: Check for incoming power at correct voltage.

CODE: br.
RESULT: Brown Out Protection engaged. Power was lost or voltage is low.
FIX: Check for incoming power at correct voltage.

CODE: L6.
RESULT: Discharge Air Too Hot.
FIX: Clean Filter or Remove Air Blockage.

CODE: LC.
RESULT: Outdoor Coil Thermistor temperature high.
FIX: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

CODE: C2.
RESULT: Indoor Air Recirculation. Large delta between thermostat and return.
FIX: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.

CODE: C5.
RESULT: Outdoor Coil temperature too high for outdoor ambient temperature.
FIX: Check for Blocked Outdoor Air or Clean Coil.

CODE: C1.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C3.
RESULT: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C4.
RESULT: Indoor Coil froze up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C6.
RESULT: Poor Unit Performance.
FIX: Check for blower motor, compressor, or electric heat operation.

CODE: C7.
RESULT: Indoor Freezing Lockout (ICT - IAT > 20) +10 Min.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

I left a live chat message on their website that my air conditioning was not working. Within 1hr a representative called me to discuss my options.
The next day he came to the house to review my needs and give me a price for a new system. Price quoted was less than I expected and the installation was completed the following day. I found their salesman and the installers very knowledgeable and easy to deal with. All my questions were answered. Everything was properly explained in regards to what unit was needed and why, along with instruction where needed for use.
The installers made sure everything was working properly before they left.

by Samta Chanana on Twintech Heating and Cooling

This is to thank Twintech Heating and Cooling for their exceptional and timely service. Mitch, their technician was very courteous and generous with his time right from his first meeting with us. He not only took the time to check everything but also educated us on why we needed what he recommended. Greg and Mitch graciously accommodated us on our requested day and time for job to be done. They were both very courteous and responsive to our needs and special requests especially in a tight spot. The job was finished neatly and on time. Thank you Twintech for your great service !

by Private User on Twintech Heating and Cooling

They came the day and time they had planned for us and were very fast and efficient! The AC works amazing and it is amazing during the heat of the summer we have already got! Thanks for everything you did for us!

by Private User on Twintech Heating and Cooling

Would recommend this company to friends and family in a heartbeat. Very professional , on time and left no mess when the job was done.

by stefany on Twintech Heating and Cooling

Great customer service. Responsive and professional. I would highly recommend Twintech, I used them previously for repair service and a new air conditioner- very satisfied.

by dianeramsden on Twintech Heating and Cooling

Our air conditioner failed. Made a call and within 15 min a technician was at our door.
The issue was fixed and many suggestions were provided.
Thanks to Mitch. Great service !

by Kazuko on Twintech Heating and Cooling

Our furnace was rattling, as soon as we put our air conditioner on this past week. We had researched looking for a company that was Registered with Better Business Bureau, and this company TwinTech, had A+ Rating. Scott, was immediately helpful via text/phone and sent his technician as soon as he was able...Mitchell/technician provided great professional service. Thank you TwinTech.
Sean and Debbie

by ANOOP on Twintech Heating and Cooling

I contacted various companies when looking to install a new furnace and I found Twintech to be transparent with their communication and approach. They had options to suit my various requirements and the price vs quality was very good. The after installation communication was also very good and they answered all queries I had.

by Private User on Twintech Heating and Cooling

My furnace broke down last month. The team was quick to respond, courteous, professional and mindful of COVID-19 concerns. I highly recommend them if you are considering replacing or servicing your HVAC equipment.

by Private User on Twintech Heating and Cooling

I was very happy with the installation and price. I would definitely recommend. Thank you Twintech.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Signs Your Amana Furnace Needs Repair

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 27, 2023

Amana furnaces, like any other heating systems, may exhibit signs of issues that require repair. Here are specific signs to look for in an Amana furnace: No Heat or Insufficient Heat: If your Amana furnace is not producing heat or not providing

Read More

Why Did My Heat Pump Shut Off On Its Own?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 26, 2023

There could be several reasons why your heat pump shut off on its own. Some common reasons include: Thermostat Settings: Check your thermostat settings to ensure that the desired temperature is set correctly. If the temperature setti

Read More

Advice Need For This AC Issue

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 23, 2023

My AC stopped blowing cold air. The unit outside seems to be working. The fan is spinning but no cold air comes out. I'm calling someone to come take a look at it today but was curious if anyone knew what it could be and give me a heads

Read More

Keeping Up With Your Furnace Maintenance: Tips from Twintech

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 22, 2024

Regular furnace maintenance is crucial for ensuring efficiency, extending its lifespan, and reducing costly repairs. At Twintech, we understand the importance of a well-maintained furnace, especially during the cold months in the Durham region. Here&

Read More