Armstrong Air is the professional's choice in home heating & cooling. Including oil & gas furnaces, air conditioners, heat pumps, package units & air handlers.


CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Jaime-Lynne in Pickering on Twintech Heating and Cooling

Greg came over at 9:30pm to rescue my daughter and I from a horrible experience with Enercare that evening. He was professional. Kind. And got us what we needed quickly and at an afford price. I would 100% recommend calling on Greg and his team for any of your heating and cooling needs in the future!!

by Matt C. Oshawa on Twintech Heating and Cooling

Installed a great hot water heater when our old one failed. When my furnace died during cold weather they showed up quickly and my house was warm before my wife got home. :)

by B Davis in Pickering on Twintech Heating and Cooling

I don’t usually right reviews but when you receive service like this I felt it was a must. Honest and fair. I Have 4 children and on Xmas eve my furnace stopped working and a gentleman came out and got me up and running so at least we would have heat for the holidays. As promised he would replace my furnace early in the new year. The job was completed on time, great price for quality furnace and extremely clean and professional job. Would have never known anyone was in the house. Not a spec of dust or mess from lugging out an old rusty furnace. If you have any ac or heating concerns twintech is your only option. I was royally impressed with and I’m sure you will be too.

by stan.marosek from Ajax on Twintech Heating and Cooling

Class Act ! These guys were professional right from the quote stage through to installation. They know their stuff and took their time to help educate me. They take pride in their work and it shows. I would recommend TwinTech Heating and Cooling to anyone. Keep up the great work !!!

by W. Lacombe in Pickering on Twintech Heating and Cooling

This Company is terrific. No high pressure sales and they deliver exactly what they promise to deliver. The new furnace is great and we now get consistent temperatures throughout the house. The installers were great and very efficient and completed the work on schedule on the promised day. Everyone representing this company was very aware of their presence in our house and worked diligently to keep our home as uninterrupted and as clean as was humanly possible. We did not need to go around the house to clean up after they left, what a nice surprise. We have had follow up by the company to ensure everything is to our satisfaction. How unusual in today's environment. The impression left by Twintech is that they care about us and our home. This is so refreshing in today's high tech world. Out thanks go out to Dave in sales and G, G, and P (the installers).

by jiinyiong in Ajax on Twintech Heating and Cooling

They were Timely and professional. They were very Knowledgeable with answering all of my questions.

by Connie in Pickering on Twintech Heating and Cooling

The entire process was prompt and professional, from the initial quote to the installation of the new furnace. The team installed the new furnace and removed the old one in approx. 4 hrs. The guys were very knowledgeable and gave me lots of information. I have used Twintech before for a new A/C installation and new I was in good hands.

by Valentine in Pickering on Twintech Heating and Cooling

The overall experience dealing with this company was great from start to finish when getting a new furnace and ac this year. Everything was clearly explained to us during our consultation with Dave and there were no surprises with added costs. The work was done as expected and their response time to inquiries were very timely generally within a few hours or less. They are all very professional and was a pleasure to do business with them. Highly recommend to anyone looking for honest quality professional service.

by Jiri in Toronto on Twintech Heating and Cooling

From the initial contact we had an excellent experience with this company and all its personnel. Dave Gergley was an excellent, helpful, sales person and solicitous of our needs. He recommended only what was required and did not up sell or make any suggestions for products that we did not need, such as a new A.C. He explained the rebate process and basically outlined how to get the best furnace at the lowest price. When it was time for installation, the technicians could not have been more considerate, careful, attentive to detail, obviously committed to safety and optimum functioning of the appliance they were setting up. We have been perfectly satisfied with the functioning of the furnace and all aspects of acquiring it from the initial contact with Dave through to the installation process and follow ups inquiring about our satisfaction. Also they initiated the rebate process and contacted the appropriate inspection agency to carry it out. We highly recommend this company for all heating and cooling needs and we will contact them again when it is time to replace our A.C.

by Drew in Pickering on Twintech Heating and Cooling

Twintech was excellent from the initial quote and throughout the install. They had a competitive rate for hot water tank and ended up buying the tank from them, had them remove the old tank and install the new one. The day of install they were prompt and out in about 2 hours. Professional , courteous really great guys. We took a look at my 30 year old furnace and they were able to offer some suggestions for future there too.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Signs Your Amana Furnace Needs a Maintenace Check

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 14, 2023

Regular maintenance is essential to ensure the efficient and safe operation of your Amana furnace. Here are some signs that indicate your furnace may need a maintenance check: Decreased Heating Efficiency: If you notice that your fur

Read More

Hazards of An Old Air Conditioner Unit

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 22, 2024

Old air conditioner units can pose several hazards due to wear and tear, outdated technology, and lack of maintenance. Here are some common hazards associated with old air conditioner units: Electrical Hazards: Over time, the electrical wiri

Read More

Serious Furnace Issues Only Professionals Can Solve

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 26, 2025

A furnace is essential for keeping your home warm and comfortable, especially during cold months. While regular maintenance can prevent many problems, certain furnace issues are too complex or dangerous for DIY repairs. Here are some serious furnace

Read More

Furnace Pilot Light is Flickering

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 7, 2025

A flickering furnace pilot light is not normal and could indicate an issue that needs attention. While some slight movement in the flame is expected, excessive flickering or an unstable flame can be a sign of problems such as: Drafts or Airflow

Read More