CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by nathans in Scarborough on Twintech Heating and Cooling

We wanted to get our AC replaced as it was 22-years old and added to this our furnace was costing more and more to repair. So, we decided to get both the furnace and AC replaced.

After going through a few quotes and product reviews we decided to go with Twintech. The three-men crew arrived early in the morning, wasted no time and got to work right away. By 2:00 pm, they were all done. I’ve found their work to be top notch and they were completely professional. I had all my questions answered to my satisfaction both during the progress of their work and at end.

I have pleasure in recommending Twintech to anyone who is looking to get their furnace or Ac replaced

Nathan S.

by Private User on Twintech Heating and Cooling

Our air conditioner died On a Saturday and within hours Dave came out to take a look and discuss replacement/repair options.
The new air conditioner was installed on the Wednesday. The new unit was installed quickly. The installers were friendly and cleaned up afterwards.
We noticed a slight leak around the furnace that night and they came out the next day and fixed the issue. It has been working great and is quieter than our previous unit.
Very satisfied and would highly recommend TwinTech.

by Nancy in Toronto on Twintech Heating and Cooling

I contacted TwinTech to replace my 20-year old A/C. Dave, their service rep, promptly replied and was at my home within 2 hours. He was friendly and knowledgeable and didn't try to upgrade or oversell their A/C units but suggested the best fit for my small 1000 feet bungalow. Although this was during a heatwave and very busy, they were able to fit me in 2 days later. The TwinTech crew installed a 1.5 ton Ducane A/C unit that is now running smoothly while maintaining a constant cooling temperature. The crew were very courteous, professional and efficient and I will definitely recommend TwinTech to family and friends. I much appreciated your great service.
Nancy M., Oshawa

by Private User on Twintech Heating and Cooling

We had a great experience. The guys who installed our a/c did a nice job. Cleaned up.

by Private User on Twintech Heating and Cooling

excellent crew, fast and efficient! Would call them again when I need a new furnace.

by Private User on Twintech Heating and Cooling

Professional, courteous and efficient, don’t need to say more than that! Use them you will not regret it.

by Private User on Twintech Heating and Cooling

TwinTech was a pleasure to deal with from the estimate through installation. We replaced a 28 year old a/c unit with one recommended by TwinTech's sales representative Dave who took the time to go over the product with us and answer any questions. The warranty is for 10 years parts and labour and they will complete the registration for you. Installation was by Greg (owner) and Mitch and Spencer who were quick and efficient and left everything clean and tidy.

by Private User on Twintech Heating and Cooling

Very professional, from the sales consultation and inspection to the final installation. Met every expectations we had for the job. A local business with great client support. We highly recommend. Twintech is a blue chip! Thanks!

by Private User on Twintech Heating and Cooling

I left a live chat message on their website that my air conditioning was not working. Within 1hr a representative called me to discuss my options.
The next day he came to the house to review my needs and give me a price for a new system. Price quoted was less than I expected and the installation was completed the following day. I found their salesman and the installers very knowledgeable and easy to deal with. All my questions were answered. Everything was properly explained in regards to what unit was needed and why, along with instruction where needed for use.
The installers made sure everything was working properly before they left.

by Samta Chanana on Twintech Heating and Cooling

This is to thank Twintech Heating and Cooling for their exceptional and timely service. Mitch, their technician was very courteous and generous with his time right from his first meeting with us. He not only took the time to check everything but also educated us on why we needed what he recommended. Greg and Mitch graciously accommodated us on our requested day and time for job to be done. They were both very courteous and responsive to our needs and special requests especially in a tight spot. The job was finished neatly and on time. Thank you Twintech for your great service !

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Most Common AC Repairs

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 9, 2024

Air conditioning systems can require various repairs over time due to wear and tear, lack of maintenance, or other issues. Some of the most common AC repairs include: Refrigerant Leaks: Refrigerant leaks can cause your AC system to malfuncti

Read More

Is My AC Unit Supposed to Be This Loud?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 15, 2024

The noise level of an AC unit can vary depending on factors such as the make and model of the unit, its age, and the environment it's installed in. However, in general, modern AC units are designed to operate relatively quietly. If your AC uni

Read More

Simple Furnace Maintenance Even You Can Do

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 6, 2025

Here's a simple guide on furnace maintenance that anyone can do: Simple Furnace Maintenance Even You Can Do A well-maintained furnace keeps your home warm and energy-efficient while preventing costly repairs. Here are a few easy maintenance

Read More

Is it safe to run a portable AC on a slightly uneaven surface?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 12, 2023

I just bought a 8000BTU unit and the hose is too small to get out a window or anywhere, I've ordered an extension and it should be here within a week, I've managed to find a space where the unit would be perfectly stable but on a tilt of mayb

Read More