CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

by nathans in Scarborough on Twintech Heating and Cooling

We wanted to get our AC replaced as it was 22-years old and added to this our furnace was costing more and more to repair. So, we decided to get both the furnace and AC replaced.

After going through a few quotes and product reviews we decided to go with Twintech. The three-men crew arrived early in the morning, wasted no time and got to work right away. By 2:00 pm, they were all done. I’ve found their work to be top notch and they were completely professional. I had all my questions answered to my satisfaction both during the progress of their work and at end.

I have pleasure in recommending Twintech to anyone who is looking to get their furnace or Ac replaced

Nathan S.

by Private User on Twintech Heating and Cooling

Our air conditioner died On a Saturday and within hours Dave came out to take a look and discuss replacement/repair options.
The new air conditioner was installed on the Wednesday. The new unit was installed quickly. The installers were friendly and cleaned up afterwards.
We noticed a slight leak around the furnace that night and they came out the next day and fixed the issue. It has been working great and is quieter than our previous unit.
Very satisfied and would highly recommend TwinTech.

by Nancy in Toronto on Twintech Heating and Cooling

I contacted TwinTech to replace my 20-year old A/C. Dave, their service rep, promptly replied and was at my home within 2 hours. He was friendly and knowledgeable and didn't try to upgrade or oversell their A/C units but suggested the best fit for my small 1000 feet bungalow. Although this was during a heatwave and very busy, they were able to fit me in 2 days later. The TwinTech crew installed a 1.5 ton Ducane A/C unit that is now running smoothly while maintaining a constant cooling temperature. The crew were very courteous, professional and efficient and I will definitely recommend TwinTech to family and friends. I much appreciated your great service.
Nancy M., Oshawa