CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Ian, Toronto on Twintech Heating and Cooling

The term excellent or incredible does not seem high enough praise for the Twintech Heating and cooling company that recently replaced our 15 year old furnace. To start with, the response from Dave at Twintech to our original pricing request was the quickest and most professional of the 5 prices we received which included two of the primary natural gas providers. The Twintech pricing was the most competitive by a considerable margin.
We had Dave visit our home to confirm all pricing which he did and scheduled us for next day installation which was not offered my the majority of the other providers.
The installation; the team arrived on time and provided coverings to all of the hardwood flooring and stairs and proceeded with the removal and reinstallation of the new furnace, the workers predicated six hours and were completed in five hours. I have to mention how courteous and polite the workers were each time we interacted with them from start to finish.
The final result was amazing, all materials were cleaned up and removed from the house and the workmanship very impressive.
One feature that really stood out for me which shows a high level of professionalism was that we had various condensation hoses from the furnace , humidifier and an air filtration unit meeting at the one drain, the installation crew ran PVC tubing including elbows along two sides of the furnace to guide the hoses into one PVC tube at the drain, it looks great!
When the install was completed and tested the Twintech technician guided us through the features and recommendation's for care of the new furnace.
We highly recommend Twintech to anyone for the outstanding service provided to us.

by Stephen, Pickering on Twintech Heating and Cooling

I didn't hesitate to call Twintech in for a 2nd time as they did an outstanding job installing my new furnace last year. This time my 18 year old air conditioner was on its last legs. Greg and the team are top notch, highly skilled technicians. The job was executed in a timely and professional manner. Greg was extremely thorough and went the extra mile to make sure everything was operating efficiently. Lastly, Dave is a true gentleman and really made the customer experience pleasurable and worry free. Always remember that good work ain't cheap and cheap work ain't good.

by Derek, Whitby on Twintech Heating and Cooling

It's so hard to find solid companies these days, but I was very pleased to find one in Twintech. Greg and his crew were very clean, respectful and professional. We were most impressed at how all the things they said they would do, were done. Sounds strange, but usually when a contractor comes to your home they say they will take care of this and that, make sure this is done, etc but when the work starts you have to constantly remind them of your previous discussions. Greg ensured every item he said he would do was done, no reminders required. The work was done right, at a fair price and on time. We will be sure to call them when our A/C unit dies (fingers crossed that's not going to happen too soon :) )

by Patrick, Toronto on Twintech Heating and Cooling

Replaced our aging hot water tank with a tankless system. Excellent work, fast efficient and clean.

Walked us through the new system and recommended maintenance schedule.

This is our second time working with TwinTech and we are very happy with the quality of their work and professionalism.

by Troy, Toronto on Twintech Heating and Cooling

Efficient work and great follow up by the team at Twin Tech. Great product and communication.

by Peter, Pickering on Twintech Heating and Cooling

On coldest night of the year our furnace quit. At 8:40 in the morning Greg arrived and gave us a diagnosis and a recommendation. By 2:30 we had a new furnace and were warm again. Great company. Great customer service. Good reasonable price.

Peter, Pickering

by New Furnace Installed on Twintech Heating and Cooling

Twin tech team was very efficient and prompt. They provided a quote within hours of request and got the job done on time. No disruption to home function. We would highly recommend this team. Job well done.

by John from Toronto on Twintech Heating and Cooling

Our furnace bit the dust, and Twintech came out to troubleshoot and diagnose the problem within a couple of hours. Mitch was super helpful, patient, and answered all of our questions. When we decided to get the furnace replaced, the crew was over first thing the next morning and did a fantastic job. Not only did they complete the job in a few hours, but they cleaned up and respected our house as they went, and answered all of our follow-up questions. I've used Twintech for our HVAC needs in the past and will continue to do so. I'd recommend them to anyone, and it feels good to support a local, family-owned business.

by Ryan k on Twintech Heating and Cooling

Dave and the Twintech team were fabulous from day 1 and helped us through the process to identifying a new furnace and AC unit. This was our first time through this process and Dave did a thorough job explaining all the components and was very patience answering all our questions. Dave provided great insights and fair pricing.

The Twintech team did an awesome installation. Very clean and efficient. I would highly recommended their service.

by Louise in Scarborough on Twintech Heating and Cooling

We had a new Amana furnace installed by Twintech and we were very pleased with the installation. It is nice to have a warm house again.