$49 / month O.A.C Including Install
$49 / month O.A.C Including Install

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

CLICK HERE FOR A FREE QUOTATION

Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by DG Sellers on Twintech Heating and Cooling

Professionally done and took care to cover all entry floors to the house for the installers to remove the old furnace and install a new furnace.
I also made recommendations of the tankless water heater that we had installed and items to address. We did not know they also installed tankless water heaters.

by Bill, Pickering on Twintech Heating and Cooling

Price was not the cheapest nor the most expensive of my quotes. It's the quality of the installation that makes for a good AC system. The twins' knowledge & professionalism was evident in the small details:
Very clean work. Greg made sure that the refrigerant level & temperature were correct. They reinstall the insulation & vapor barrier around the wall. The outside electrical cords were secured to the wall. Proud to support this local company. Thank you.

by Taz on Twintech Heating and Cooling

Great team of guys came to do the work. Very professional. Arrived on time worked very efficiently and were very clean. They answered any questions we had without hesitation. The air conditioner works great and is so quiet. I highly recommend them and they don't try to up-sell anything right from the start.

by Jordan on Twintech Heating and Cooling

The service was prompt, professional and very courteous. Competitive price. Would highly recommend this company.

by David on Twintech Heating and Cooling

Excellent workmanship, and quick response. Would recommend Twintech to anyone.

by Todd Whyte on Twintech Heating and Cooling

My existing 15-yr old A/C went down on me during the first major heatwave of the season. Researched my options, as well as a few different installers, and decided on Twintech.

They gave me confidence right from the beginning. Extremely knowledgeable. Their communication was excellent - always responded to questions quickly. Given we were in a heatwave, they were fully booked. However, within days they were able to fit me in due to a cancellation. Upon learning that the Amana unit I was getting installed was on backorder, TwinTech went to bat for me with the manufacturer and was able to get me the next model up within a day, for the same price - Amazing!

As far as the installation was concerned, I couldn’t be more impressed. These guys were clearly very experienced and did a fantastic job. Very clean, polite, timely & informative. They even thoroughly sealed all the exposed gaps in my ductwork. I’ve had plenty of heating and cooling work done in the past and have never used the same contractor twice because I’ve never been very impressed. However, from now on, I’ll always be contacting Twintech first!

by Jordan Arnott, Courtice on Twintech Heating and Cooling

They were very friendly and took care of everything. The install looks great (and works great), they were very knowledgeable. Installed our a/c efficiently despite the difficult install location both inside and outside and they made it work.

by Lori Ellis on Twintech Heating and Cooling

Phenomenal service, so glad I found these guys a few years back after being "hosed" badly by 3 other companies. I've recommended them to so many, and they all are so thankful.

by Jonathan Rogoza on Twintech Heating and Cooling

This company is fantastic. Dave came out and gave me a very honest and reasonable quote, unlike a quote received from another company. I had a bunch of questions that were easily answered and when I had questions regarding heating/cooling a previously unheated room above the Garage, Dave arranged for Greg to come out for an assessment of this new space and gave me his recommendation along with his professional thoughts on all of my options.

These guys have been nothing but Professional, honest and helpful along the way. I can't recall the two other guys doing the install, but they were great as well. Good workmanship, everything was cleaned up and everything functions as promised. I could go on and on about my experience, but it's all positive so what more could you want?

Give them a call, see for yourself. If I had to buy another furnace/AC or heat pump, they'd be my first call.

by Private User on Twintech Heating and Cooling

I hired twin tech to convert my townhouse heating from electric to gas and install a furnace and a/c unit. I had talked with many other vendors, and received several quotes, but chose them, and very happy I did. Here are some of the reasons why:
1. They were realistic about the timeline for the work, when they could start and how long it would take. (They said upfront, it was their busy season and would need to get back to me in 3 weeks, which they did):
2. They had a quote with options for me. They were clear about the entertainment of what they would and would not do (they’d build duct work, id need another contractor to box in ductwork). This allowed me to plan as I was my own general contractor for my renovations).
3. They spoke to me in a language I understood, neither too technical nor too simple. They answered all my questions as I had them. Everyone is so lovely to work with, the sales team and the contractors who are worked in my home.
4. It’s been 4 m since the work was complete. They still answer my emails and my furnace is working very well!

I unabashedly recommend! Price, customer care and quality workmanship were all amazing!

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

What is a Heat Pump and How Does it Work?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 31, 2019

A heat pump is an electrical device that pulls heat from one place and transfers it to another. This type of device has been used in Canada and around the world for decades. Both refrigerators and air conditioners use this type of device. Do not

Read More

Why Choose an Amana Furnace?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 5, 2024

Choosing an Amana furnace could be a good option for several reasons: Reliability: Amana has a reputation for producing reliable HVAC (Heating, Ventilation, and Air Conditioning) equipment. Their furnaces are built to last and are known for

Read More

Low Airflow Problems? Here are 3 Possible Causes

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 21, 2017

You may be running your air conditioner or your heating system. Whichever it is, you certainly expect to get a certain amount of airflow when you have your hands up to the vents. When that airflow level drops and the temperature in your home cha

Read More

The Remarkable Durability of Amana Heat Pumps

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 18, 2025

When choosing a heating and cooling system for your home, durability should be a top priority. A long-lasting unit not only saves you money on repairs and replacements but also provides consistent comfort and peace of mind. Among the many HVAC

Read More