Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by peter in Whitby on Twintech Heating and Cooling

Very impressed with this company. They show up on time , kept my place clean and after they left it looks like they were never there. Very professional team. Those people know what they doing . Their installation was on the highest standard. They are very knowledgeable especially they're worker Peter. I strongly recommend this company to everybody. After the installation I receive the call making sure I'm satisfied with their products and their job. Bravo!!!

by James in Bowmanville on Twintech Heating and Cooling

Greg and his brother were referred to us by a friend. They arrived when they said they would, did an exceptional job and left the place as tidy or tidier then they found it. Their professionalism is only surpassed by their kind and friendly demeanor. Even after several calls to help me with my high tech thermostat I feel that I could always call with any concern (No one responds to my texts as quickly as Greg) and have a friendly helpful response. I found out their grandfather started the company and now as a 3rd generation company, they are doing their grandfather proud. I would highly recommend Twintech over any other hvac company out there.

by RJW in Ajax on Twintech Heating and Cooling

Thanks to the guys at Twintech Heating for a great job installing a new hot water tank. They set a time and day to remove the old tank and install the new one. They were on time and had the work done quickly and cleaned up after they were finished. Excellent work and great value.

by Marilyn in Milton on Twintech Heating and Cooling

In November, we contacted Twintech for a quote on a high efficiency furnace plus installation. Dave, the sales representative for the company was very friendly and informative. Upon arrival at our home, he willingly showed us his company licenses, clearly explained the operation of a high efficiency furnace and answered all our questions to our satisfaction. As well, Dave was the only sales representative that we contacted that was willing to make the arrangements for an energy audit. For us, this was a big plus as we found the government rebate program somewhat confusing to navigate. The furnace was installed on the date that was arranged in an efficient and professional manner by Greg (the owner) and Peter. Both men worked diligently, throughout a long day to complete the job and upon finishing, left the job site immaculate. When a neighbour raised concerns about the furnace venting location, Greg located an alternative location and resolved the situation with diplomacy. We chose the Napoleon furnace for its excellent warrant;y on the heat exchanger and because it was made in Canada! In addition, to the furnace warranty, Twintech offered us a 5 year warranty on labour which speaks to the quality and pride this team has in their workmanship. It has been over a month now (with some of the coldest January days on record) since we have had the furnace installed. The furnace runs quietly and distributes heat more evenly throughout our 90 year old Toronto home. We can't speak highly enough of the Twintech team and are very satisfied with their workmanship and job ethics. We have no hesitation about recommending them.

by Barry in Toronto on Twintech Heating and Cooling

What more could you ask for! Grant and Greg Dainty provided a professional,diligent and thorough approach to the installation of my furnace. I would highly recommend there services.

by Hector in Scarborough on Twintech Heating and Cooling

Last week our Furnace failed overnight. We called Twintech to help us get it running again. They did a really thorough check on it, and got it running in less than an hour. Given that it was an old Furnace (+20 years old), we were giving two options: repair it or replace it. Instead of doing a repair on it that could break in a week or two, they recommended us to change it. I like that they were honest on the recommendation, not forcing a new furnace on us. At the end we went with a new Furnace. Twintech solutions service & salesman gave us recommendation on the size of the unit and many options that could work for our home. They ended up doing an excellent work in our furnace, replacing the filter to a better option and replacing some pieces that had water damage. They cleaned after themselves and leave everything even better than what they found. They even went far and beyond tiding up the hose connections that we had on the basement.

by Ryan Doherty in Whitby on Twintech Heating and Cooling

I am in the process of finishing my basement and wanted to make sure I got the low hanging duct work fixed in advance. After reviewing 5 quotes I selected Twintech to award the contract to. The price was competitive however what won me over was Grant's (co-owner) attention to detail and his ability to focus on what my goals and priorities were for the project. His team completed the job over 3 days as there was significant duct work changes and the relocation of all of the equipment. They also completed the job with little downtime so we weren't left overnight without heat during freezing winter temperatures.

by Private User from Oshawa on Twintech Heating and Cooling

My father woke up to no heat one Saturday morning. We had a few names that friends had recommended but while checking out the companies' ratings on HomeStars, we found Twintech with great ratings too. The other companies either didn't get back to us or didn't have time to come at such short notice. TwinTech made the time in their schedule for what they judged to be an emergency: no heat in the home of an elderly person. At no extra fee for a short notice, weekend visit. They recommended an upgraded furnace unit and explained that we would qualify for a rebate that would bring the price down to that of a lower model. They set us up with the rep from the MNR that covers the rebate so that we didn't have to deal with the paperwork & phone calls ourselves. Installation was quick, efficient, & smooth. We were so pleased with their service we ordered a new water heater too. Both are working great (efficient & quiet!) & my father is safe & comfortable. We can't say enough about how pleased we are with their service. We have already recommended them to others.

by joe calabro in Pickering on Twintech Heating and Cooling

Twintech Heating & Cooling. I just want to say thanks for helping me . My Furnace stopped working. And l phone Dave Getgley he set me up with Greg. What an amazing team they did a great job in setting me up with a new Furnace. Anyone that needed a new Furnace these are the guys to call. Thanks again for a job well done.

by Peter from Ajax on Twintech Heating and Cooling

Our home has had poor heating and air conditioning the past couple of years. Dave recommended a Goodman solution with more power than we had. Grant and Greg installed the units in late November. Heating is better than ever. We have a warm home again and look forward to the winter. Can't wait to see how the AC runs in 2018. Job was super clean and professionally done. Highly recommended.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Debris is Covering My AC Unit

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 9, 2024

It's essential to keep your AC unit clear of debris to ensure it functions properly. Here's what you can do: Turn Off Power: Before doing anything, turn off the power to your AC unit to avoid any accidents. Remove Debris: Car

Read More

Exhaust Hose Extension Help on Portable A/C

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 21, 2023

I bought a black and decker portable A/C very similar to the one in these pictures with those exact parts. It has a 5. 9” exhaust hose. I am looking for parts to extend the exhaust hose but I feel like I'm missing a part. I boug

Read More

How Will a Newly Installed AC Unit Effect Your Home?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 24, 2024

Installing a new air conditioning (AC) unit can have several effects on your home, both positive and potentially negative, depending on various factors. Here are some common effects: Improved Comfort: The most immediate and noticeable effect

Read More

What's Should I Do When My AC Breaks Down?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - June 26, 2024

When your AC breaks down, here are the steps you should follow: 1. Check the Basics Thermostat Settings: Ensure the thermostat is set to cooling mode and the temperature is set correctly. Power Supply: Check if the AC unit is receiving pow

Read More