$49 / month O.A.C Including Install
$49 / month O.A.C Including Install

24 / 7 Emergency Service Available. Call Us Now: 1.844.894.6832

Durham Region Air Conditioning Repair, Service and Installation

CLICK HERE FOR A FREE QUOTATION

Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Roy in Pickering on Twintech Heating and Cooling

I was referred to Twintech by a neighbour and was not disappointed. Not only was the customer service excellent their workmanship was second to none. Greg and Grant work extremely clean covering the pathway to the furnace room, labeling the essential parts, left the area spotless and were efficient. They cleaned up the mess left by the previous installers (wiring, improperly installed AC coil, and gaps in venting etc). They also ran through the operation of the new furnace and gave me some maintenance tips. Greg and Grant are professional and all around good guys. I will definitely recommend their service to anyone without hesitation.

by Peter Buck, Pickering on Twintech Heating and Cooling

Very satisfied with service from Twintech , beginning with all the information provided by Dave , which helped make the decision much easier . Installation was very smooth & done on time as promised & cleanup was well done . Would definitely recommend this company & use them again for any future needs . Well done.

by Angela from Ajax on Twintech Heating and Cooling

Twintech Heating & Cooling Inc. came in and replaced my 39 year old furnace with a beautiful Napoleon variable high efficiency furnace! Their work was efficient and professional and they were a pleasure to deal with, from sales to installation! I would highly recommend them.

by Scott and Sandra in Ajax on Twintech Heating and Cooling

After receiving numerous quotes to replace my old furnace and AC unit (which was 20 years old) I went with Twintech. Dave, in sales, answered questions professionally and promptly and worked diligently in order to secure my business. Installation was scheduled the week after and Greg and Peter showed up, as scheduled, and did a fine job installing both units. The site was left tidy and neat. I would highly recommend Twintech for your furnace and AC work.

by Linda from Whitby on Twintech Heating and Cooling

I chose TwinTech because they installed my new furnace a few years ago and did a great job. When they installed my new A/C, they replaced all parts -- the copper pipes, the housing on top of the furnace and the wiring. (Apparently, the wiring for my old A/C was insufficient.) Their pricing was competitive. The sales representative came to see me within a few hours of my call. My new A/C was installed a few days later and I couldn't be happier with Twintech's professionalism and work. I would recommend TwinTech to any homeowner.

by george polychronis from Whitby on Twintech Heating and Cooling

Had a great experience with this company. Great price and great customer service. You wont be disappointed with twintech. Discussed the job with Greg while he was installing who was extremely informative and obviously enjoys the work he does.

by Nuzio in Markham on Twintech Heating and Cooling

I needed my AC unit relocated due to upcoming landscape work. I reached out to the Twintech team through Homestars. Dave connected with me immediately to discuss the project and various options. We decided the best option was to mount the unit on the wall. Greg was in touch with me the same day as well and we scheduled the work for later that same week. This was a small job so I did not think I would get immediate attention. The Twintech team exceeded my expectations in every respect. They were very knowledgeable and friendly. The team arrived exactly on time on the scheduled day and worked efficiently to get the job done quickly. I would definitely use Twintech again for any Heating and AC projects.

by Leslie B, Pickering on Twintech Heating and Cooling

I have used Greg Dainty for over 15 years in 3 different homes, for heating, cooling, pool heaters, appliances and bbq lines. Greg has always been so professional, friendly and the workmanship nothing short of fantastic. Greg has always discussed my options and fixing versus replacing, giving his honest opinion and what works best for me cost effective wise and long term. I have valued his opinion so much and have not trusted my gas needs with anyone since using him. I have also referred him to many of my friends and family and have always been so thankful with how well and quickly he looks after us all. I hold Greg in the highest regard and would recommend him to anyone with complete confidence!

by Marcel M, Whitby ON on Twintech Heating and Cooling

Really nice honest guys. It was a pleasure to do business with a company that does exactly what they say they’re going to do! My basement was cleaner after they installed my new furnace and AC. Thanks again Greg and Grant and for doing such a great job.

by George In Pickering on Twintech Heating and Cooling

5 star service!! I had twin tech install a high efficiency furnace and hot water tank at my home. I am taking time to write this review as a thanks for what I viewed as next level service that went above and beyond. Prior to installation they explained my specific options without pushy sales tactics and up front costs. Greg and Grant replaced a large portion of the duct work (built in their own shop) that had rusted over the years which resulted in a great looking job. It was a pleasure to work with people are passionate and take pride in their work. Following the installation they explained all aspects and maintenance of the new equipment. Products have worked flawlessly. Thanks again Greg and Grant! Highly recommend!!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

What's the Best Way to Use My Gree Heat Pump to Save on Electricity?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 15, 2023

To maximize energy savings and efficiency when using a Gree heat pump, you can follow these tips: Set the Thermostat Wisely: Use a programmable or smart thermostat to maintain consistent temperatures. Set lower temperatures during th

Read More

When's the Last Time You Had Your Furnace Serviced?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 27, 2024

When’s the Last Time You Had Your Furnace Serviced As temperatures drop, your furnace becomes the unsung hero of your home, keeping your space warm and comfortable. But like any hardworking appliance, it requires regular maintenance to perf

Read More

Is My Furnace Unit Oversized?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 19, 2024

An oversized furnace can lead to several issues, such as increased energy costs, uneven heating, and shorter equipment lifespan. To determine if your furnace unit is oversized, consider the following signs: 1. Short Cycling If your furnace f

Read More

Amana Heat Pump Maintenance Tips

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 9, 2023

Maintaining your Amana heat pump is crucial for optimal performance and energy efficiency. Here are some general maintenance tips to help you keep your Amana heat pump in good condition: Regularly Clean or Replace Air Filters: Dirty

Read More