The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Robert, Pickering on Twintech Heating and Cooling

Had new furnace installed and ran into some difficulties but the contractor responded in a timely and efficient manner - after further service calls were made, a reasonable resolution was found.

by Brian Burns, Whitby on Twintech Heating and Cooling

The work was done quickly efficiently neatly and professionally. Pleased with the service, information, product, and the company.

by Geoff, Port Perry on Twintech Heating and Cooling

Great sales member named Dave came in told us some amazing items and how they would be priced installed an all. We couldn’t believe it! The next day the ac was installed, that day one employee named Greg told us that our furnace was working way to hard and was causing us to use way too much gas. So two days later they came in an installed a new furnace!

by MB, Ajax on Twintech Heating and Cooling

Installation was done quickly and professionally. The new furnace is quiet and provides even heat.

by Richard from Oshawa on Twintech Heating and Cooling

They removed and discarded old furnace. Installed new furnace. Installed air intake pipe, that had never been installed by builder, no charge. Replaced loose hose on floor with hard pipe and rerouted it to drain, no charge. Almost 33% cheaper then quote from Enercare, which was the company we dealt with and had insurance with for 8 years. No yearly fee for cleaning/insurance, saves 300 a year. Courteous, professional, fast, and friendly. My wife and I have been recommending them to everyone we know and meet, and will continue to do so. Thanks for everything, Twintech!!!

by Darcy from Pickering on Twintech Heating and Cooling

This company was great to deal with. Our furnace went down and they installed a new furnace the next day with a lot of professionalism!

by gillian hooton from Uxbridge on Twintech Heating and Cooling

Finally! An honest company with highly knowledgeable and informative staff. Had a furnace service and found multiply errors in our system from an amateur installer. Very fair price to correct problems and will definitely use again.

by dflynn in Ajax on Twintech Heating and Cooling

Had to replace the heating & a/c unit in a condo apartment dwelling. this company recommended by the property manager and president of the condo building. found their workmanship and attention to details very good and very thorough. were able to resolve small problems and situations and happy to feel the heat in my unit. it's pricey, but happy was done by a very professional service. thank you.

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Humidity issues with ducted Mitsubishi heat pump

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 5, 2023

Hello, wondering if others have experienced difficulty maintaining comfortable humidity using a Mitsubishi hyper heat ducted system. I think the heart of the matter is that they try to be too efficient and can maintain temp well but ignore the imp

Read More

How to Safely Operate Your Heat Pump

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 8, 2023

Operating a heat pump safely is important for both efficiency and the well-being of your home. Heat pumps are versatile systems that provide both heating and cooling, and they require proper care to ensure optimal performance. Here are some guideline

Read More

Preventing AC Damage: Tips for Long-Lasting Performance

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 26, 2024

Preventing AC Damage: Essential Tips for Long-Lasting Performance Preventing damage to your air conditioner doesn’t just keep your home cool—it also helps you avoid costly repairs and extend the life of your system. Here’s what y

Read More

Why Frequent Furnace Cleaning Are Important

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 21, 2025

Frequent furnace cleaning is essential for several reasons, ranging from efficiency to safety. Here are the key benefits of regular furnace maintenance: 1. Improves Efficiency A clean furnace operates more efficiently. Over time, dirt, du

Read More