The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by silvercola from Toronto on Twintech Heating and Cooling

I received three quotes before deciding to choose Twintech. Dave's prices was much more reasonable than the competitors. I most appreciated their honest recommendations. Others tried to oversell their products and services. Thank you Dave!

by Shane from Whitby on Twintech Heating and Cooling

They had the best price and did a great job on the installation. Recommend them to anyone.

by gabnai7 on Twintech Heating and Cooling

It was a amazing and professional high quality job
Friendly and very helpful representatives
Thank you for understanding my concern
And explain very well
Overall we pleased with your service
Tanks

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accommodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

by Bill, Oshawa on Twintech Heating and Cooling

We are very happy with our new furnace. The service was excellent the guys worked 6 hours straight through and there was no mess at all they took the old furnace box’s etc with them they then explained everything to us they were very helpful and pleasant , when we need a new air conditioner we know who to call!

by Ken, Bomanville on Twintech Heating and Cooling

The crew from sales to installation was very professional and had great attention to detail

by Tracy, Pickering on Twintech Heating and Cooling

We couldn’t have been more impressed with Twintech - from our first service call with Mitch who took the time to thoroughly diagnose the issue with our furnace, to Dave who proposed a well thought out solution to meet our needs and finally Greg and team who acted quickly to install given we had no heat.


We did our due diligence by soliciting quotes from alternate providers and were shocked and disappointed by the aggressive and manipulative tactics used.


Twintech was honest in their approach, detailed in their product knowledge, reasonably priced, diligent in their follow-up and valued our business.


Well done Twintech! You made this a positive experience for us and our new furnace works beautifully!

by Skapoor, Ajax on Twintech Heating and Cooling

We recently purchased an Amana high efficiency furnace and humdifier through Twintech. The work was completed very professionally and the quality of the workmanship was high. There was some additional sheet metal work required to complete the installation, which they were able to complete themselves. Overall I am very pleased with the work and would highly recommend Twintech for a furnace replacement.

by Steve, Oshawa on Twintech Heating and Cooling

We were very pleased with every aspect of the work that was done. They were very professional and polite. They arrived when they said they would and job was completed on estimated time


We would highly recommend them to whoever needed a recommendation


We have a very large dog and they were very understanding and respectful of him being around