The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Patrick, Toronto on Twintech Heating and Cooling

The blower on our furnace stopped working leaving us with a cold house. Dave from TwinTech responded immediately to our HomeStars service request. From beginning to end Dave was nothing but helpful, friendly and professional, he did a great job of walking us through the quote and scope of work.


The replacement of the furnace went smoothly. The Guys did a great job, everyone was very friendly and polite. There were no hiccups, or unexpected costs. The only surprise was they left the work area cleaner than it was before they started.


Was a great experience with the whole TwinTech team. Its been a couple of months since the new furnace has been installed and its working great!

by Ed, Whitby on Twintech Heating and Cooling

I heard about TwinTech when researching new furnaces at furnaceprices.ca. After contacting them about my broken down furnace, Dave came to my house the next day to assess my situation and requirements for a new furnace. He recommended one that had stainless steel heat exchangers which sold me since my previous furnace had issues with a rusted secondary heat exchanger that had to be replaced. Dave also set me up with an appointment with an energy audit company so that I could take advantage of a rebate to help improve the energy efficiency of my home and get some money back. A few days later, Greg, Grant, and Mitch came to install the new furnace and remove the old one. When delivering and removing the furnaces, they were very careful not to damage my floors and walls, and even laid out red carpeting to protect the floors. They were very friendly and professional. The installation was completed in the time they said it would take and they cleaned up their work areas. Within a week, Dave called to follow-up to see how everything was going. I have already recommended them to several friends and family members who may need new furnaces soon.

by Fred, Toronto on Twintech Heating and Cooling

Twintech did a great job, from Dave the Sales Rep to the Office staff and The Professional Technicians who did the installation. They were professional, courteous, knowledgable and informative. From beginning to follow up we were completely satisfied with everything. Thanks Again. Sincerely The Laytons

by Elle, Oshawa on Twintech Heating and Cooling

Great product, great service, great follow-up. The Twintech Heating and Cooling arranged removal of my existing oil tank and they installed the new gas furnace Amana (made in USA). I am very happy with the final result and support I received throughout the process. My thanks go to the entire Twintech team for their professionalism, great communication and follow-up.

by John & Linda, Ajax on Twintech Heating and Cooling

We've had Twintech provide us with work in the past, for an inground pool heater and required rough-in for a new gas stove. More recently they provided the same friendly, professional, timely and clean installation of our new furnace.

by Bill, Whitby on Twintech Heating and Cooling

Reasonable price and the workmanship was prompt and timely and the employees were great to deal with.

by Nadia, Toronto on Twintech Heating and Cooling

The sales process was friendly, informative, and very consultative. They worked hard to earn our business by taking a careful look around our home to assess our needs, providing a lot of information about the product, and answering all our questions and finding the right solution for our home at a competitive price. They prepared us very well for what to expect on installation day, and the installation went very smoothly - no surprises, all very professional! They gave us a call after installation to ensure we were happy with the work. We're very happy that we chose to work with TwinTech to get our new furnace.

by Private User on Twintech Heating and Cooling

Twintech promptly responded to request for quotation. They were thorough and helpful in explaining options. The quote was very competitive. Installation of new furnace was very professionally completed. Excellent work.

by Rita, Scarborough on Twintech Heating and Cooling

When our old oil furnace finally broke down we decided it was time to finally convert to natural gas and finally install central air conditioning at the same time. Knowing it was going to be a significant investment for us, we wanted to make the right choice. Twintech came highly recommended by a friend and we were not disappointed. From the first contact with the salesperson, until the final touches on the installation, we were so pleased with their service. Everyone from the company was so friendly, efficient and a pleasure to deal with. Best of all, the cost was very competitive. We would certainly recommend Twintech to anyone requiring HVAC work in their home.

by Bob S, Pickering on Twintech Heating and Cooling

Mitch from Twintech came out for our annual furnace inspection. We found him to be friendly, conscientious & he left the work area clean. We were also very impressed with the thoroughness of the job he did. This is the 2nd job we’ve had Twintech do for us & have been very happy with the results for each. We highly recommend this company. Thank you, Mitch, Dave & Greg.