The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

by nathans in Scarborough on Twintech Heating and Cooling

We wanted to get our AC replaced as it was 22-years old and added to this our furnace was costing more and more to repair. So, we decided to get both the furnace and AC replaced.

After going through a few quotes and product reviews we decided to go with Twintech. The three-men crew arrived early in the morning, wasted no time and got to work right away. By 2:00 pm, they were all done. I’ve found their work to be top notch and they were completely professional. I had all my questions answered to my satisfaction both during the progress of their work and at end.

I have pleasure in recommending Twintech to anyone who is looking to get their furnace or Ac replaced

Nathan S.

by Private User on Twintech Heating and Cooling

Our air conditioner died On a Saturday and within hours Dave came out to take a look and discuss replacement/repair options.
The new air conditioner was installed on the Wednesday. The new unit was installed quickly. The installers were friendly and cleaned up afterwards.
We noticed a slight leak around the furnace that night and they came out the next day and fixed the issue. It has been working great and is quieter than our previous unit.
Very satisfied and would highly recommend TwinTech.

by Nancy in Toronto on Twintech Heating and Cooling

I contacted TwinTech to replace my 20-year old A/C. Dave, their service rep, promptly replied and was at my home within 2 hours. He was friendly and knowledgeable and didn't try to upgrade or oversell their A/C units but suggested the best fit for my small 1000 feet bungalow. Although this was during a heatwave and very busy, they were able to fit me in 2 days later. The TwinTech crew installed a 1.5 ton Ducane A/C unit that is now running smoothly while maintaining a constant cooling temperature. The crew were very courteous, professional and efficient and I will definitely recommend TwinTech to family and friends. I much appreciated your great service.
Nancy M., Oshawa