If you're looking for help fixing your daikin air conditioner, look no further! Our comprehensive daikin air conditioner repair guide will explain common issues, provide troubleshooting tips, and show you how to read your model's error codes.


CODE: A0.
RESULT: External protection device activated. External protection device connected to the terminal strip T1-T2 of indoor unit is activated.

CODE: A1.
RESULT: Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB.

CODE: A3.
RESULT: Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch.

CODE: A4.
RESULT: Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor.

CODE: A5.
RESULT: High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor.

CODE: A6.
RESULT: Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor.

CODE: A7.
RESULT: Malfunction of swing flap motor Failure of swing flap motorm, Defect of indoor unit PCB Jammed swing mechanism/blade.

CODE: A8.
RESULT: Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage.

CODE: A9.
RESULT: Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact.

CODE: AA.
RESULT: Heater overheat 26WH is activated.

CODE: AF.
RESULT: Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline.

CODE: AH.
RESULT: Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB.

CODE: AJ.
RESULT: Malfunction of capacity setting (Indoor unit PCB) Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB.

CODE: C1.
RESULT: Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver.

CODE: C4.
RESULT: Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger.

CODE: C5.
RESULT: Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger.

CODE: C6.
RESULT: Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver.

CODE: C7.
RESULT: Front panel driving motor fault Defect of front panel driving motor Defect of limit switch.

CODE: C9.
RESULT: Malfunction of suction air thermistor Defect of connector contact Defect of thermistor for suction air.

CODE: CA.
RESULT: Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for discharge air.

CODE: CC.
RESULT: Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor.

CODE: CJ.
RESULT: Malfunction of thermostat sensor in remote controller Defect of remote controller thermistor Malfunction due to noise Defect of remote controller PCB. Outdoor Unit.

CODE: E0.
RESULT: Protection devices actuated (unified) Protection device connected to outdoor PCB actuated Defect of protection device connector contact.

CODE: E1.
RESULT: Defect of outdoor unit PCB Malfunction due to noise Defect of outdoor unit PCB?.

CODE: E3.
RESULT: Actuation of high pressure switch (HPS) Dirty outdoor unit heat exchanger and suction filter Defect of HPS Clogged refrigerant piping Defect of connector contact.

CODE: E3.
RESULT: System No.1. Actuation of high pressure switch (HPS). Dirty outdoor unit heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact Outdoor Unit.

CODE: E4.
RESULT: Actuation of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connecting connector Defect of outdoor unit PCB.

CODE: E5.
RESULT: Overheat of inverter compressor motor Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: E5.
RESULT: Inverter compressor motor lock Inverter compressor lock Incorrect wiring.

CODE: E6.
RESULT: STD compressor motor overcurrent/lock Closed stop valve STD compressor lock.

CODE: E6.
RESULT: System No.1 Compressor overcurrent Defect of EXP. valve Defect of compressor Shortage of refrigerant amount.

CODE: E7.
RESULT: Malfunction of outdoor unit fan motor. Faulty contact of fan motor connector. Defect of fan motor, Defect of fan motor driver.

CODE: E8.
RESULT: Overcurrent of inverter compressor, Defect of compressor, Defect of outdoor unit PCB Defect of inverter main circuit capacitor Defect of power transistor.

CODE: E9.
RESULT: Malfunction of electronic expansion valve coil Defect of electronic expansion valve Defect of connector contact Defect of outdoor unit PCB.

CODE: EA.
RESULT: Malfunction of four way valve Defect of four way valve Defect of outdoor unit PCB Shortage of gas Defect of thermistor.

CODE: EC.
RESULT: Malfunction of entering water temperature Malfunction of cooling water temperature. Defect of thermistor. Defect of outdoor unit PCB.

CODE: EF.
RESULT: Malfunction of thermal storage unit Defect of electronic expansion valve of thermal storage unit Defect of thermal storage PCB.

CODE: F3.
RESULT: Malfunction of discharge pipe temperature Shortage of gas. Defect of connector contact. Clogged refrigerant piping Defect fo discharge pipe thermistor.

CODE: F6.
RESULT: Abnormal high pressure in cooling Defect of outdoor unit fan motor Defect of electronic expansion valve Defect of heat exchanger thermistor, Defect of outdoor unit PCB.

CODE: F6.
RESULT: Refrigerant overcharged Refrigerant overcharged Disconnection of heat exchanger thermistor Disconnection of outdoor air thermistor Disconnection of liquid pipe thermistor.

CODE: H0.
RESULT: Malfunction of sensor system of compressor, Harness is disconnected, or defective connection Defect of PCB.

CODE: H1.
RESULT: Malfunction of humidifier unit damper, Defect of limit switch Defect of damper.

CODE: H3.
RESULT: Malfunction of high pressure switch (HPS), Defect of high pressure switch. Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H4.
RESULT: Malfunction of low pressure switch (LPS), Defect of low pressure switch Broken wire. Defect of connector contact, Defect of outdoor unit PCB.

CODE: H5.
RESULT: Malfunction of compressor motor overload thermistor Defect of connector contact. Defect of compressor motor overload thermistor.

CODE: H6.
RESULT: Malfunction of position detection sensor, Faulty contact of compress or cable. Defect of compressor, Defect of outdoor unit PCB.

CODE: H7.
RESULT: Malfunction of outdoor fan motor signal Faulty contact of fan wiring Defect of fan motor driver Defect of fan motor.

CODE: H8.
RESULT: Malfunction of compressor input (CT) system Defect of power transistor. Defect of reactor. Faulty wiring of inverter system Defect of outdoor unit PCB.

CODE: H9.
RESULT: Malfunction of outdoor air thermistor. Defect of connector contact Defect of thermistor for outdoor air.

CODE: HC.
RESULT: Malfunction of (hot) water temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of thermistor for water temperature.

CODE: HF.
RESULT: Alarm in thermal storage unit with ice Thermal storage group defective wiring Defect of setting Excess of thermal storage tank numbers.

CODE: HJ.
RESULT: Malfunction of thermal storage tank water level Low water level Defect of switch setting Water level detecting sensor failure Defect of connector contact Outdoor Unit.

CODE: J1.
RESULT: Malfunction of pressure sensor Defect of pressure sensor connector contact. Defect of pressure sensor. Defect of outdoor unit PCB.

CODE: J2.
RESULT: Malfunction of current sensor of compressor Defect of current sensor Defect of outdoor unit PCB Defect of compressor.
CODE: J3.
RESULT: Malfunction of discharge pipe thermistor. Defect of connector contact Defect of outdoor unit PCB Defect of discharge pipe thermistor.

CODE: J4.
RESULT: Malfunction of low pressure equivalent saturated temperature sensor system Defect of connector contact Defect of thermistor Defect of outdoor unit PCB (Multi-split, Super-multi ).

CODE: J5.
RESULT: Malfunction of suction pipe thermistor Defect of connector contact Defect of outdoor unit PCB Defect of suction pipe thermistor.

CODE: J6.
RESULT: Malfunction of heat exchanger thermistor Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: J7.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J8.
RESULT: Malfunction of liquid pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of liquid pipe thermistor.

CODE: J9.
RESULT: Malfunction of gas pipe thermistor (Refrigerant circuit and others) Defect of connector contact Defect of outdoor unit PCB Defect of gas pipe thermistor.

CODE: JA.
RESULT: Malfunction of high pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of high pressure sensor.

CODE: JC.
RESULT: Malfunction of low pressure sensor Defect of connector contact Defect of outdoor unit PCB Defect of low pressure sensor.

CODE: JE.
RESULT: Malfunction of sub-tank thermistor Defect of connector contact Defect of outdoor unit PCB Defect of sub-tank thermistor.

CODE: JF.
RESULT: Malfunction of heating thermistor for heat exchanger Defect of connector contact Defect of outdoor unit PCB Defect of heat exchanger thermistor.

CODE: JH.
RESULT: Malfunction of oil temperature thermistor Defect of connector contact Defect of outdoor unit PCB Defect of oil temperature thermistor.

CODE: L0.
RESULT: Malfunction of inverter system Shortage of power supply capacity Defect of inverter PCB Defect of power transistor.

CODE: L1.
RESULT: Malfunction of inverter PCB Defect of compressor wiring Blown fuse Defect of outdoor unit fan motor Defect of inverter PCB.

CODE: L3.
RESULT: Electrical box temperature rise Fin temperature rise due to short-circuit Defect of power transistor Defect of outdoor unit fan Defect of outdoor unit PCB.

CODE: L4.
RESULT: Malfunction of inverter radiating fin temperature rise Fin temperature rise due to short-circuit Defect of fin thermistor.

CODE: L5.
RESULT: Inverter instantaneous overcurrent (DC) Closed stop valve Defect of compressor.

CODE: L6.
RESULT: Inverter instantaneous overcurrent (AC) Overcharge of refrigerant amount Defect of compressor Shortage of power supply capacity Defect of inverter unit.

CODE: L8.
RESULT: Overcurrent of inverter compressor Abnormal high pressure rise due to clogged refrigerant circuit and others Defect of compressor.

CODE: L9.
RESULT: Malfunction of inverter compressor startup Faulty of pressure equalization Defect of compressor wiring Defect of compressor.

CODE: LA.
RESULT: Malfunction of power transistor Defect of power transistor Defect of inverter PCB Defect of compressor.

CODE: LC.
RESULT: Malfunction of transmission between outdoor unit PCB and micro-computer Defect of grounding connection Defect of outdoor unit PCB Malfunction due to noise.

CODE: LC.
RESULT: Malfunction of transmission between control and inverter PCB Defect of connector contact Defect of inverter PCB Malfunction due to noise Defect of outdoor unit control PCB.

CODE: P0.
RESULT: Shortage of refrigerant amount (thermal storage unit) Shortage of refrigerant Clogged refrigerant piping Outdoor Unit.

CODE: P1.
RESULT: Power voltage imbalance, open phase Open phase Voltage imbalance between phases Faulty main circuit capacitor. Defect of wiring contact.

CODE: P2.
RESULT: Automatic refrigerant charge operation stop Closed stop valve. Closed valve of refrigerant tank.

CODE: P3.
RESULT: Malfunction of thermistor in electrical box Electrical box temperature rise (ambient temperature rise) Defect of fin thermistor, Defect of outdoor unit PCB.

CODE: P4.
RESULT: Malfunction of radiating fin temperature sensor Defect of radiating fin thermistor Defect of wiring contact Defect of outdoor unit PCB.

CODE: P8.
RESULT: Heat exchanger freezing protection during automatic refrigerant charging (Close the refrigerant cylinder. Start again from step 1.).

CODE: P9.
RESULT: Malfunction of fan motor (humidifier unit) Defect of fan motor Broken relay harness Defect of outdoor unit PCB Defect of connector contact.

CODE: P9.
RESULT: Automatic refrigerant charge operation completed.

CODE: PA.
RESULT: Broken wire of heater (humidifier unit) Defect of heater unit Defect of outdoor unit PCB Defect of thermistor.

CODE: PA.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of master unit is empty.

CODE: PC.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 2 is empty.

CODE: PE.
RESULT: Automatic refrigerant charge operation nearly completed.

CODE: PH.
RESULT: Malfunction of temperature (humidifier unit) Defect of heater unit Defect of thermistor Defect of connector contact Defect of outdoor unit PCB.

CODE: PH.
RESULT: Empty refrigerant cylinder during automatic refrigerant charging Refrigerant cylinder of slave unit 1 is empty.

CODE: PJ.
RESULT: Malfunction of capacity setting (Outdoor unit PCB) Capacity setting adaptor is not installed Improper capacity setting adaptor Defect of outdoor unit PCB.

CODE: PJ.
RESULT: Improper combination between inverter and fan driver Mistake of inverter PCB Mistake of control PCB Mistake of inverter fan PCB System.

CODE: U0.
RESULT: Shortage of refrigerant Shortage of refrigerant Closed stop valve Clogged refrigerant piping.

CODE: U1.
RESULT: Reverse phase, open phase Reverse phase, open phase of power wiring Wrong wiring. Defect of outdoor unit PCB.

CODE: U2.
RESULT: Defect of power supply voltage or instantaneous power failure. Defect of power supply voltage Instantaneous power failure Defect of wiring contact.

CODE: U3.
RESULT: Check operation not executed. Check operation not executed.

CODE: U3.
RESULT: Malfunction of transmission Malfunction due to noise Defect of outdoor unit PCB Wrong wiring.

CODE: U4.
RESULT: Malfunction of transmission between indoor and outdoor unit Defect or indoor-outdoor transmission wiring Malfunction due to noise Defect of indoor unit PCB and outdoor unit PCB.

CODE: U5.
RESULT: Malfunction of transmission between indoor unit and remote controller Defect of remote controller wiring Defect of indoor unit PCB Malfunction due to noise Defect of remote controller main/sub setting.

CODE: U6.
RESULT: Malfunction of transmission between indoor units Faulty wiring Defect of indoor unit PCB Malfunction due to noise.

CODE: U7.
RESULT: Malfunction of transmission between main body micro-computer. INV micro-computer Harness disconnection/broken wire between PCB Defect of outdoor unit PCB.

CODE: U7.
RESULT: Malfunction of transmission between outdoor units Defect of wiring between outdoor units Defect of outdoor unit switch setting Defect of wiring between outdoor thermal storage units.

CODE: U8.
RESULT: Malfunction of transmission between remote controllers Defect of remote controller main/sub setting Defect of remote controller wiring. Defect of remote controller PCB Others.

CODE: 77.
RESULT: System No. 1 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 78.
RESULT: System No. 2 Malfunction of fan inter lock Defect of relay contact Broken wire.

CODE: 7A.
RESULT: System No. 2 Malfunction of current sensor of compressor Defect of current sensor. Defect of compressor Defect of outdoor unit PCB.

CODE: 7C.
RESULT: System No. 2 Malfunction of pump inter lock Cooling water pump interlock actuated.

CODE: 80.
RESULT: Malfunction of entering water temperature thermistor. Defect of connector contact. Defect of entering water temperature thermistor.

CODE: 81.
RESULT: Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 82.
RESULT: System No. 1 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 83.
RESULT: System No. 2 Malfunction of refrigerant thermistor Defect of connector contact Defect of refrigerant thermistor.

CODE: 84.
RESULT: System No. 1 Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 85.
RESULT: System No. 2. Malfunction of heat exchanger thermistor. Defect of connector contact. Defect of heat exchanger thermistor.

CODE: 86.
RESULT: System No. 2. Malfunction of discharge pipe thermistor. Defect of connecting connector Defect of discharge pipe thermistor.

CODE: 88.
RESULT: System No. 2. Malfunction of discharge pipe temperature. Shortage of gas. Defect of discharge pipe thermistor Defect of connector contact. Clogged refrigerant piping.

CODE: 89.
RESULT: Malfunction of brazed-plate heat exchanger freezing Dirty heat exchanger. Shortage of refrigerant amount Defect of thermistor.

CODE: 8A.
RESULT: System No. 2 Malfunction of leaving water temperature thermistor Defect of connector contact Defect of leaving water temperature thermistor.

CODE: 8E.
RESULT: System No. 1 Malfunction of suction pipe thermistor 1 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8F.
RESULT: System No. 1 Malfunction of suction pipe thermistor 2 for heating Defect of connector contact Defect of suction pipe thermistor.

CODE: 8H.
RESULT: Abnormal high hot water temperature Three-way valve malfunction. Defect of thermistor Defect of water temperature setting.

CODE: 90.
RESULT: Abnormal chilled water quantity, abnormal AXP. Shortage of water volume Disconnection of AXP.

CODE: 91.
RESULT: System No. 2 Malfunction of electronic expansion valve Defect of connector contact Defect of electronic expansion valve coil.

CODE: 92.
RESULT: System No. 2 Malfunction of suction pipe thermistor Defect of connector contact Defect of suction pipe thermistor.

CODE: 94.
RESULT: Malfunction of transmission (between heat reclaim ventilation unit and fan unit) Defect of fan unit PCB Defect of connecting wire between (1) and (2).

CODE: 95.
RESULT: System No. 1 Malfunction of inverter system Defect of fan inverter unit.

CODE: 96.
RESULT: System No. 2 Malfunction of inverter system Defect of fan inverter unit.

CODE: 97.
RESULT: Malfunction of thermal storage unit Defect of thermal storage unit.

CODE: 98.
RESULT: Malfunction of thermal storage brine pump Actuation of thermal storage brine pump overcurrent (OC).

CODE: 99.
RESULT: Malfunction of thermal storage brine tank Low water level of thermal storage brine tank System.

CODE: U9.
RESULT: Malfunction of transmission (other system) Defect of communication between other indoor unit and outdoor unit Other indoor unit electronic expansion valve failure.

CODE: UA.
RESULT: Defect of indoor/outdoor power supply Wrong model connections Wrong PCB connected Improper power supply Defect of PCB.

CODE: UA.
RESULT: Malfunction of field setting Malfunction of field setting by remote controller Defect of remote controller wiring Defective connection of optional device Defect of indoor unit PCB.

CODE: UA.
RESULT: Improper combination of indoor and outdoor units Excess of connected indoor units Malfunction of field setting Uncanceled service mode. Defect of outdoor unit PCB.

CODE: UA.
RESULT: Remote temperature setting wire disconnection Remote temperature setting wire disconnection Defect of connector contact.

CODE: UC.
RESULT: Malfunction of setting of centralized controller address. Address duplication of centralized controller.

CODE: UE.
RESULT: Malfunction of transmission between indoor unit and centralized controller Malfunction of wiring between indoor unit and centralized controller Defect of setting of group number Defect of indoor unit PCB.

CODE: UF.
RESULT: Wiring and piping mismatch Improper connection of transmission wiring between indoor-outdoor units and outdoor-outdoor units.

CODE: UH.
RESULT: Malfunction of system Improper connection of transmission wiring between indoor- outdoor units and outdoor-outdoor units Defect of indoor and outdoor unit PCB (RA: Mismatching indoor and outdoor units, Defect of voltage, Freeze protection in other indoor unit (k).

CODE: UJ.
RESULT: Malfunction of transmission (Accessory devices) Defect of accessory devices Faulty wiring.

CODE: M1.
RESULT: Malfunction of centralized remote controller PCB. Defect of centralized remote controller PCB.

CODE: M8.
RESULT: Malfunction of transmission between optional controllers for centralized control Other centralized control power disconnection Centralized control reset switch ON Defect of transmission wiring. Central remote controller address change.

CODE: MA.
RESULT: Improper combination of optional controllers for centralized control Improper combination of optional controllers for centralized control More than one master controller is connected Faulty setting of centralized control Defect of centralized control.

CODE: MC.
RESULT: Address duplication, improper setting Address duplication of central remote controller.

CODE: 60.
RESULT: External protection device actuated Actuation of external protection device Defect of output signal wiring Defect of control PCB.

CODE: 64.
RESULT: Malfunction of indoor air thermistor Defect of connecting connector Defect of thermistor for indoor air Defect of control PCB.

CODE: 65.
RESULT: Malfunction of outdoor air thermistor Defect of connector contact Defect of control PCB Defect of outdoor air thermistor.

CODE: 6A.
RESULT: Malfunction of damper system Defect of connector contact Defect of damper motor Defect of limit switch Defect of control PCB.

CODE: 70.
RESULT: System No. 2 Compressor overload Shortage of refrigerant amount Defect of connector contact Leakage of four way valve.

CODE: 71.
RESULT: System No. 2 Compressor overcurrent Shortage of refrigerant amount Short-circuit Defect of compressor.

CODE: 72.
RESULT: System No. 2 Fan motor overcurrent Defect of fan motor connector contact Defect of fan motor Defect of PCB.

CODE: 73.
RESULT: System No. 2 Malfunction of high pressure (HPS) actuated Dirty heat exchanger Clogged refrigerant piping Defect of HPS Shortage of water volume Defect of connector contact.

CODE: 74.
RESULT: System No. 2 Malfunction of low pressure switch (LPS) Clogged refrigerant piping Shortage of gas. Defect of connector contact Defect of LPS.

CODE: 75.
RESULT: System No. 2 Malfunction of low pressure sensor Defect of connector contact Defect of PCB Defect of low pressure sensor.

CODE: 76.
RESULT: System No. 2 Malfunction of high pressure sensor Defect of connector contact Defect of PCB Defect of high pressure sensor.


See What Our Customers Are Saying:

by Craig in Whitby on Twintech Heating and Cooling

I called Twintech during the Covid 19 crisis because our furnace was broken and it was still very cold during the nights. Dave answered all of my questions by phone but wanted to come have a look but only if our family felt comfortable having someone visit during the uncertainty surrounding the pandemic and was able to attend that very same affternoon.

He was very courteous and informative but most importantly he respected his and our safety by wearing medical gloves in our home and maintaining proper physical distancing. He reviewed the various options of the products that suited our needs going over not only price but quality of workmanship, warrantees and where the product was manufactured which were all important factors in making such a large purchase. You could tell that Dave had been in this industry for a very long time.

The installation was done by a fine young gentleman the very next day and we now have a toasty warm home to ride out this crisis in while humming along at 96% efficiency!

I would recommend this very professional, small family business for anyone in need of HVAC equipment or maintenance.

by Lucy in Markham on Twintech Heating and Cooling

My special thanks to Twintech teams! They had replaced my furnace and A/C, and installed a new humidifier for me 2 weeks ago. Dave, the sales manager, not only provided me with an honest quote on the best HVAC products with best quality and warranties, he also arranged portable heaters for me and sent supporting docs to energy company for energy audit. Above and beyond service!

Greg, Grant, Mitch had worked tirelessly and professionally to perform the HVAC installation. They worked with professional tools, and performed proper measurement readings after installation. They are very patient with all my questions, and very pleasant to communicate.

Great work guys! This company sure knows their products and they stand behind their services. My home comfort level has improved! I am glad that I can support an ethical and honest local family business.

by ddame on Twintech Heating and Cooling

Professional, flexible on price and delivered on time...well done. All you can ask for when getting a new furnace.

by nicole.el.thorn on Twintech Heating and Cooling

The work was done quickly and professionally. Workers were really polite and easy to work with.
Product works great!

by Gary in London on Twintech Heating and Cooling

Furnace broke down on a Wednesday, shopped around for prices and Friday Twintechs name came up from a referral from my wife's work. Called Dave 11 am, he came over around 1 pm. Gave me a very good price, I accepted. The guys were there two hours later to take the old furnace out and install the new one. All finished by 6:30pm. Finally heat.
They were very pleasant and helpful. As a result we are doing our A/C later this year with this company.

by Shawn L in Whitby on Twintech Heating and Cooling

After some extensive research, we settled on Twintech for our new furnace. The service - from Dave's initial visit - through to the installation was absolutely fantastic.

Dave was super-patient with our many questions, did not try to "up-sell" us into buying things we don't need, knowledgeable, friendly and all-around an excellent Advisor.

I've forgotten the names of the installers but they were superb as well. They showed up on-time, did all the work with no mess or intrusion, removed the old furnace and installed the new one in one day; all with no impacts to our day-to-day life.

I cannot recommend Twintech enough, especially over any of 'bigger guys' who tried to sell us a bunch of thing we don't need. Twintech were fantastic and my wife and I are very pleased with our purchase.

by Stephen from Pickering on Twintech Heating and Cooling

From the minute I met Dave and discussed my new furnace needs I knew I was in good hands. He was patient, knowledgeable and very professional through the quotation process.

Grant and Greg did an outstanding job on the install. They did a great job of explaining the defects with my old furnace. The quality of the installation was excellent and the attention to detail was on another level. The old adage “You get what you pay for” couldn’t be more true as I feel I received great value, skilled expertise and high quality customer service. I highly recommend Twintech for all your heating and cooling needs.

by Arthur on Twintech Heating and Cooling

Glad to have found a not-too-big local firm that provided the needed expertise, quality workmanship, and competitive pricing as well. In and out in one day, removed the old units, did a nice job installing all of the new units, and left no debris. Even have a service contract that far outshined the big company offerings. Would definitely recommend them.

by Leriksen on Twintech Heating and Cooling

Appreciated a quick response to my request. Dave and Greg were very professional and made the experience seamless.

by petesalmon938 from Pickering on Twintech Heating and Cooling

Very professional through the entire process. Installation and removel was done on a sloppy winter day, they put down runners on the floors and stairs and when they left, there wasn;t any sign of someone being in our house. Furnace works great as promised.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Preventing a Total Furnace Breakdown

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 5, 2025

Preventing a total furnace breakdown is crucial for maintaining a warm and comfortable home, especially during the colder months. Here are some essential steps to ensure your furnace runs efficiently and avoids unexpected failures: 1. Schedule Reg

Read More

Expert HVAC Services in Scugog

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 16, 2025

When it comes to heating and cooling services in Scugog, Twintech Heating and Cooling stands out as a trusted provider with years of experience in the industry. Whether you need a furnace repair, air conditioning installation, or routine HVAC main

Read More

Regular Furnace Maintenance: Keep Your Home Safe and Warm

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 8, 2024

The Importance of Regular Furnace Maintenance: Keep Your Home Safe and Warm As the colder months approach, ensuring that your furnace is functioning properly is crucial for keeping your home warm, comfortable, and safe. Regular furnace maintenance

Read More

Benefits of a Brand New Heat Pump

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 25, 2024

Investing in a brand new heat pump can offer several benefits, including: Energy Efficiency: New heat pumps are designed to be more energy-efficient than older models, which can lead to lower utility bills over time. They utilize advanced te

Read More