The Payne gas furnace has built in diagnostics and is designed to assist with the identification and correction of faults. The furnace utilizes an LED, to describe its condition.This can be viewed through a port on the blower access panel. You can take corrective action in response to any faults indicated by the LED.


The number of short flashes of the LED represents the first digit of the two digit fault code. The number of long flashes of the LED represents the second digit of the fault code.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 11.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY- Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 12.
RESULT: BLOWER CALIBRATION LOCKOUT- Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 13.
RESULT: LIMIT SWITCH LOCKOUT- Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 14.
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours. Refer to #34.

CODE: 21.
RESULT: INVALID MODEL SELECTION- Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 22.
RESULT: SETUP ERROR- Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 23.
RESULT: INVALID BLOWER AIRFLOW SELECTION- Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 24.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary voltage (24VAC) wiring. PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind.

CODE: 31.
RESULT: Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch - Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 33.
RESULT: LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 34.
RESULT: IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 41.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE- Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 42.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE- Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 43.
RESULT: PRESSURE SWITCH CALIBRATION FAULT- Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 44.
RESULT: BLOWER CALIBRATION FAULT- Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 45.
RESULT: CONTROL CIRCUITRY LOCKOUT -Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

by Jaime-Lynne in Pickering on Twintech Heating and Cooling

Greg came over at 9:30pm to rescue my daughter and I from a horrible experience with Enercare that evening. He was professional. Kind. And got us what we needed quickly and at an afford price. I would 100% recommend calling on Greg and his team for any of your heating and cooling needs in the future!!

by Matt C. Oshawa on Twintech Heating and Cooling

Installed a great hot water heater when our old one failed. When my furnace died during cold weather they showed up quickly and my house was warm before my wife got home. :)

by B Davis in Pickering on Twintech Heating and Cooling

I don’t usually right reviews but when you receive service like this I felt it was a must. Honest and fair. I Have 4 children and on Xmas eve my furnace stopped working and a gentleman came out and got me up and running so at least we would have heat for the holidays. As promised he would replace my furnace early in the new year. The job was completed on time, great price for quality furnace and extremely clean and professional job. Would have never known anyone was in the house. Not a spec of dust or mess from lugging out an old rusty furnace. If you have any ac or heating concerns twintech is your only option. I was royally impressed with and I’m sure you will be too.

by stan.marosek from Ajax on Twintech Heating and Cooling

Class Act ! These guys were professional right from the quote stage through to installation. They know their stuff and took their time to help educate me. They take pride in their work and it shows. I would recommend TwinTech Heating and Cooling to anyone. Keep up the great work !!!

by W. Lacombe in Pickering on Twintech Heating and Cooling

This Company is terrific. No high pressure sales and they deliver exactly what they promise to deliver. The new furnace is great and we now get consistent temperatures throughout the house. The installers were great and very efficient and completed the work on schedule on the promised day. Everyone representing this company was very aware of their presence in our house and worked diligently to keep our home as uninterrupted and as clean as was humanly possible. We did not need to go around the house to clean up after they left, what a nice surprise. We have had follow up by the company to ensure everything is to our satisfaction. How unusual in today's environment. The impression left by Twintech is that they care about us and our home. This is so refreshing in today's high tech world. Out thanks go out to Dave in sales and G, G, and P (the installers).

by jiinyiong in Ajax on Twintech Heating and Cooling

They were Timely and professional. They were very Knowledgeable with answering all of my questions.

by Connie in Pickering on Twintech Heating and Cooling

The entire process was prompt and professional, from the initial quote to the installation of the new furnace. The team installed the new furnace and removed the old one in approx. 4 hrs. The guys were very knowledgeable and gave me lots of information. I have used Twintech before for a new A/C installation and new I was in good hands.

by Valentine in Pickering on Twintech Heating and Cooling

The overall experience dealing with this company was great from start to finish when getting a new furnace and ac this year. Everything was clearly explained to us during our consultation with Dave and there were no surprises with added costs. The work was done as expected and their response time to inquiries were very timely generally within a few hours or less. They are all very professional and was a pleasure to do business with them. Highly recommend to anyone looking for honest quality professional service.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

My Panasonic Heat Pump Suddenly Shut Off

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 21, 2024

If your Panasonic heat pump has suddenly shut off, there are several potential reasons for this issue. Here are some troubleshooting steps you can take to identify and possibly resolve the problem: Check the Power Supply: Ensure that

Read More

The Exceptional Efficiency of an Amana Heat Pump

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 15, 2025

When you choose an Amana heat pump for your home in the Durham Region or Toronto, you’re choosing a system designed for maximum comfort with minimal energy use. Twintech Heating & Cooling installs Amana systems that consistently outperfo

Read More

One System for Both Heating and Cooling

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 10, 2025

When it comes to keeping your home comfortable year-round, most homeowners rely on two separate systems: a furnace or boiler for heating in the winter, and an air conditioner for cooling in the summer. But what if you could have a single, energy-e

Read More

Common Mistakes When Getting a New Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 20, 2025

Here are some common mistakes people make when getting a new furnace, and how to avoid them: Choosing the Wrong Size A furnace that's too big will cycle on and off frequently, leading to uneven heating and higher energy bills. Too smal

Read More