In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Private User on Twintech Heating and Cooling

They came the day and time they had planned for us and were very fast and efficient! The AC works amazing and it is amazing during the heat of the summer we have already got! Thanks for everything you did for us!

by Private User on Twintech Heating and Cooling

Would recommend this company to friends and family in a heartbeat. Very professional , on time and left no mess when the job was done.

by stefany on Twintech Heating and Cooling

Great customer service. Responsive and professional. I would highly recommend Twintech, I used them previously for repair service and a new air conditioner- very satisfied.

by dianeramsden on Twintech Heating and Cooling

Our air conditioner failed. Made a call and within 15 min a technician was at our door.
The issue was fixed and many suggestions were provided.
Thanks to Mitch. Great service !

by Kazuko on Twintech Heating and Cooling

Our furnace was rattling, as soon as we put our air conditioner on this past week. We had researched looking for a company that was Registered with Better Business Bureau, and this company TwinTech, had A+ Rating. Scott, was immediately helpful via text/phone and sent his technician as soon as he was able...Mitchell/technician provided great professional service. Thank you TwinTech.
Sean and Debbie

by ANOOP on Twintech Heating and Cooling

I contacted various companies when looking to install a new furnace and I found Twintech to be transparent with their communication and approach. They had options to suit my various requirements and the price vs quality was very good. The after installation communication was also very good and they answered all queries I had.

by Private User on Twintech Heating and Cooling

My furnace broke down last month. The team was quick to respond, courteous, professional and mindful of COVID-19 concerns. I highly recommend them if you are considering replacing or servicing your HVAC equipment.

by Private User on Twintech Heating and Cooling

I was very happy with the installation and price. I would definitely recommend. Thank you Twintech.

by Dorothy on Twintech Heating and Cooling

Had furnace and air conditioning unit put in. They did an excellent job great price and everything clean as can be, I was very pleased

by Barry on Twintech Heating and Cooling

All winter I have had an issue with very little heat reaching the 2nd floor of our home. After this past winter ended I decided to look into this. I found Twintech Heating and Cooling on line and started the process. After explaining my problem I had a call form Twintech and the tech came out and walked through things with me. The problem was the heating vent pipe had been dropped down in size by someone years ago causing little heat reaching the 2nd floor. Further into checking out the older furnace and AC they found a few things not properly installed by the last install of the old furnace and also that the AC was on it's last legs. I asked for a quote and waited a few days and we decided to go ahead with Twintech. They called a few days before to set up an installation time and date. The day of the install the guys were a half hour early which was a plus. The day of the install was great, the guys worked away removing the old furnace and AC.After which they installed the new furnace and AC. After they cleaned up the basement with all their tools and scrap metal etc. they came back inside to walk thru what they did. They also tested both the furnace and cooling systems to make sure everything worked and I the customer was happy. I now have heat on the 2nd floor for next winter. The guys from Twin tech were very professional. Their work habits and knowledge of the job was excellent. Their workmanship was just excellent, it was just up there with my standards as a homeowner. I am very pleased to have chosen Twintech for my new furnace and AC.. If I had to rate this experience with Twintech this company is a 10 in my books.Product,workmanship and customer care says it all.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

The Essential Guide to Air Conditioner Home Ownership

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 31, 2024

Owning an air conditioner is not just about enjoying cool, comfortable air during the sweltering summer months—it's about ensuring your unit runs efficiently, lasts longer, and provides value for your investment. Whether you're a new ho

Read More

How Does an AC Unit Normally Function?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 5, 2024

An air conditioning (AC) unit works by extracting heat from inside a building and transferring it outside, thereby cooling the indoor air. Here's a basic rundown of how a typical AC unit functions: Evaporation: The process begins with a

Read More

Are Portable ACs at all useful if you have no other options?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 21, 2023

I have a friend who lives in an apartment that does not allow window units to be placed. Seems their only option is one of the portable ACs that stand on the floor that you just use the vent / exhaust hose going out the window. This would only

Read More

Most Common AC Error Codes

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 4, 2024

Air conditioners (AC) come with built-in error codes that help diagnose issues. Here's a list of some of the most common AC error codes and their meanings: General AC Error Codes E1: Indoor unit temperature sensor error E2: Indoor unit

Read More