In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Leriksen on Twintech Heating and Cooling

Appreciated a quick response to my request. Dave and Greg were very professional and made the experience seamless.

by petesalmon938 from Pickering on Twintech Heating and Cooling

Very professional through the entire process. Installation and removel was done on a sloppy winter day, they put down runners on the floors and stairs and when they left, there wasn;t any sign of someone being in our house. Furnace works great as promised.

by alenahawco from Whitby on Twintech Heating and Cooling

Dave was very pleasant to deal with and Twintech responded quickly when our furnace needed to be replaced ASAP. Installation was done on time and the crew were neat and tidy. We now have a great furnace that suits the needs of our family.

by Isatta From Pickering on Twintech Heating and Cooling

When your furnace kicks in over the holidays and you're not sure where to turn.. I'm so thankful that this company returned my phone call. I appreciated their transparency and clarity which allowed me to make an informed decision. With various quotes thrown at you, it can be difficult to make the right decision and trust the solutions offered by different companies. TwinTech spoke the truth and delivered on their word. Neat, timely and clean service; the peace of mind I needed during a very cold holiday season. I highly recommend them!

by eryna from Oshawa on Twintech Heating and Cooling

Pulling a old unit out and installing a modern heating system! Required drilling holes in the wall for the newer pipes. We went from 70% (I am willing to bet it was far less due to lack of maintenance and just old) to 96% newer . It now feels warmer and more pressure and we use to run extra heaters and feel as though they are not necessary!

by silvercola from Toronto on Twintech Heating and Cooling

I received three quotes before deciding to choose Twintech. Dave's prices was much more reasonable than the competitors. I most appreciated their honest recommendations. Others tried to oversell their products and services. Thank you Dave!

by Shane from Whitby on Twintech Heating and Cooling

They had the best price and did a great job on the installation. Recommend them to anyone.

by gabnai7 on Twintech Heating and Cooling

It was a amazing and professional high quality job
Friendly and very helpful representatives
Thank you for understanding my concern
And explain very well
Overall we pleased with your service
Tanks

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accommodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Panasonic Heat Pump Service Oshawa

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 21, 2025

When it comes to efficient home climate control, few solutions match the reliability and innovation of Panasonic heat pumps. Whether you're aiming to reduce your energy bills or looking for an eco-friendly way to heat and cool your home, Panas

Read More

The Dangers of a Leaking Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 28, 2025

A leaking furnace can pose significant risks to your home and family. Here's a detailed look at the dangers, causes, and solutions to protect your household: 1. Dangers of a Leaking Furnace a. Carbon Monoxide Poisoning A leaking furnac

Read More

Amana Heat Pumps for Sale in Oshawa

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 26, 2025

Looking for a dependable, energy-efficient way to heat and cool your home year-round At Twintech Heating & Cooling, we proudly offer top-of-the-line Amana heat pumps to homeowners across the Durham Region and Toronto. With professional installat

Read More

Durham Region Heat Pump Experts You Can Trust

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 8, 2025

When it comes to your home comfort, you deserve more than just a contractor—you deserve true experts you can trust. At Twintech Heating & Cooling, we’ve built our reputation as the go-to heat pump specialists in the Durham Region a

Read More