In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by alenahawco from Whitby on Twintech Heating and Cooling

Dave was very pleasant to deal with and Twintech responded quickly when our furnace needed to be replaced ASAP. Installation was done on time and the crew were neat and tidy. We now have a great furnace that suits the needs of our family.

by Isatta From Pickering on Twintech Heating and Cooling

When your furnace kicks in over the holidays and you're not sure where to turn.. I'm so thankful that this company returned my phone call. I appreciated their transparency and clarity which allowed me to make an informed decision. With various quotes thrown at you, it can be difficult to make the right decision and trust the solutions offered by different companies. TwinTech spoke the truth and delivered on their word. Neat, timely and clean service; the peace of mind I needed during a very cold holiday season. I highly recommend them!

by eryna from Oshawa on Twintech Heating and Cooling

Pulling a old unit out and installing a modern heating system! Required drilling holes in the wall for the newer pipes. We went from 70% (I am willing to bet it was far less due to lack of maintenance and just old) to 96% newer . It now feels warmer and more pressure and we use to run extra heaters and feel as though they are not necessary!

by silvercola from Toronto on Twintech Heating and Cooling

I received three quotes before deciding to choose Twintech. Dave's prices was much more reasonable than the competitors. I most appreciated their honest recommendations. Others tried to oversell their products and services. Thank you Dave!

by Shane from Whitby on Twintech Heating and Cooling

They had the best price and did a great job on the installation. Recommend them to anyone.

by gabnai7 on Twintech Heating and Cooling

It was a amazing and professional high quality job
Friendly and very helpful representatives
Thank you for understanding my concern
And explain very well
Overall we pleased with your service
Tanks

by Linda, Toronto on Twintech Heating and Cooling

My 19 year old furnace stopped working when the cold weather hit in November, and I was left without heat. I interviewed several companies and found TWINTECH HEATING and COOLING to be very knowledgeable, quick to respond to my inquiries and very competitively priced.
Dave provided all of the information and pricing ahead of time and set up the appointment for the installation. Greg and Mitch arrived on time to do the installation and worked quickly and efficiently to complete the job.
After the completion of the installation, Dave followed up to ensure that everything was working well and that I didn't have any concerns.
Overall, this was a low-stress and flawless experience from start to finish. I would highly recommend TWINTECH HEATING and COOLING to anyone that requires a new furnace.

by Sean, Whitby on Twintech Heating and Cooling

Our 20 year old furnace broke down during the first cold weekend this past November and our usual HVAC company never returned our phone call. Their loss, missing out on a sale since we didn't want to spend much fixing an old furnace and our 40 year old air conditioner was also long overdue for replacement. We proceeded in obtaining three different quotes for furnace and air conditioner replacement, and proceeded with the one we received from Twintech.


Dave was friendly, knowledgable and accommodating to our schedule and provided with us with a price that fell in the middle of the three quotes that we had. We felt that the Amana furnace and air conditioner he quoted us on were the best products and value offered to us and felt most comfortable with the professionalism and reputation of Twintech.


Greg, Grant and Mitch were at our house for installation the day after we decided to proceed. The guys were friendly and informative, the job was completed efficiently and workmanship appears excellent. Our house is certainly much more comfortable with the new two-stage variable speed Amana furnace compared to the old clunker! And, we're looking forward to enjoying the new air conditioner once summer rolls around again. Thanks Twintech!

by Bill, Oshawa on Twintech Heating and Cooling

We are very happy with our new furnace. The service was excellent the guys worked 6 hours straight through and there was no mess at all they took the old furnace box’s etc with them they then explained everything to us they were very helpful and pleasant , when we need a new air conditioner we know who to call!

by Ken, Bomanville on Twintech Heating and Cooling

The crew from sales to installation was very professional and had great attention to detail

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

New Years Resolutions for Your Home

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 22, 2021

People commonly make New Year’s resolutions for things that concern their personal lives. This year, however, you might want to consider making resolutions that involve keeping your home a safe and enjoyable place from the outside world.Here are so

Read More

Is My Amana Heat Pump Good For the Environment?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 30, 2024

I can provide some general information that might help you evaluate the environmental impact of your Amana heat pump. Energy Efficiency: Heat pumps, including those made by Amana, are generally more energy-efficient than traditional heating

Read More

Is Your HVAC System Making Your Home Dusty?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 15, 2018

We all know the struggle of cleaning your home from top to bottom only to wake up a few days later and notice that dust has already begun to accumulate once again. It’s an annoying process that keeps us continually reaching for the duster da

Read More

Why Buy a Heat Pump For My Durham Home

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 27, 2025

When it comes to keeping your Durham Region home comfortable year-round, choosing the right HVAC system is crucial. One of the most efficient and versatile options available today is the heat pump. At Twintech Heating and Cooling, we believe a

Read More