In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Paul, Toronto on Twintech Heating and Cooling

This is the second time we have had Twintech to our house. A couple of summers ago they were in for an issue with our air conditioning. This time it was our furnace having an issue. It was shutting off randomly and not coming back on. Greg came right away and took the time to investigate thoroughly and explain what was going with the furnace. Both times I have been thoroughly impressed with their speed, customer service, and quality of work. I HIGHLY recommend Twintech.

by Private User on Twintech Heating and Cooling

Extremely happy.
So we were in no rush to replace our old units and took the time to do some research and get a number of quotes.
Twintech came in at around the middle of the pack for price but what convinced us to go with them was Bob, the representative that came to our house. Bob was by far the most professional of all the reps that we met with. He took the time to explain everything, what would work best for us and why. He really did seem very knowledgeable and enthusiastic about his stuff.
As promised on the day of install the crew showed up on time and got to work with minimal impact on us
..they were professional, clean, tidy and got the system up and running ahead of schedule...they made a couple of adjustments to the system to optimize it for our house.
The crew left the house clean and tidy.
Bob the rep showed up to check in and give us a few tips ..
It's been a week since install and all is good.
Our overall experience with Twintech has been excellent from start to finish and I wouldn't hesitate to recommend them.
Thank u.

by Private User on Twintech Heating and Cooling

It was a refreshing experience interacting with the Twintech team. From Bob, the sales consultant, who articulated in layman's terms all the options available and reasons for making any selection. This was done without the prevailing pressure tactics so commonplace today.

Before proceeding Mitch, the technician, at our request conducted a service check on our 30 yr old furnace. His report was positive indicating no urgency to replace it. Again no pressure tactics.

Three days after first meeting with Bob, the installation team of Greg and
Spencer completed the installation within the planned time frame.

A very professional, courteous and transparent team which delivered on their promise. I highly recommend Twintech.

by Private User on Twintech Heating and Cooling

Initial contact with sales resulted in an immediate response, which led to a timely installation. Both sales and installers were all very professional. I have no hesitation in recommending TWINTECH.

by Private User on Twintech Heating and Cooling

I had a great experience with TwinTech. The company offered a reasonable quote, and performed a quick and clean installation. The installer Greg was experienced, professional and courteous. He explained the services he performed and gave recommendations on maintain the new furnace.

The salesman Bob was honest
and professional and educated me on how to achieve optimal performance.

All communication from them was quick and they came the following day. I was pleased with the service and would recommend them.

by Lousan, Ajax on Twintech Heating and Cooling

From quote, to installation, to follow up, Twintech provided excellent service. I would highly recommended their services.

by John, Pickering on Twintech Heating and Cooling

I had a really great experience with these guys. The salesman Bob was clearly very knowledgeable about everything to do with heating and cooling a home, spent a lot of time with us going over the details of the job, never rushed us and came back after the install to make sure we were happy. The installation crew was excellent, they covered the floors all the way from outside down to the basement furnace room, kept the place clean, got the work done on time and we’re very friendly. I’ve got 15 years in the contracting/ construction industry and these guys are one of the most professional company’s I’ve dealt with. Great company!

by Debra Robertson on Twintech Heating and Cooling

Had great service and clean-up was good. Was happy with my salesman. They were very friendly and helpful. I needed a new furnace as our was over 20 years old. The furnace and air-conditioner work great and they are very quiet. I am very pleased with the service and product I received.

by Private User on Twintech Heating and Cooling

Met with Dave for the sales process and he was great about explaining and going over everything to us. The install happened very quickly and the team were super professional and friendly. We are very happy with this company and their services and we definitely recommend them to others. Thankful my sister recommended them to me!

by Private User on Twintech Heating and Cooling

Reviews for Twintech were good, and they did not disappoint. After an initial visit to discuss the suitable AC unit for replacement, an installation date was available in just a couple of days, and everything was installed without a hitch. Highly recommended

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Undersized heat pump?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 28, 2023

Our previous house was a 1968 split level 1600 total sq feet with basement and we had a 13 seer carrier ac 2 to worked well. We also had new triple pane windows and white exterior. Our new house is a bungalow old windows and brown exterior so m

Read More

Does My AC Accommodate My Home Size?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 11, 2024

To determine if your air conditioning (AC) system adequately accommodates the size of your home, you'll need to consider several factors: Square footage of your home: Calculate the square footage of your home, including all living spaces

Read More

Whitby Furnace Maintenance

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 8, 2025

When it comes to ensuring your home stays warm and comfortable during the harsh Ontario winters, reliable furnace maintenance is essential. Twintech Heating & Cooling is Whitby’s trusted HVAC service provider, offering expert furnace mainte

Read More

Benefits of an Indoor A/C Unit

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 19, 2023

Indoor air conditioning units, also known as ductless mini-split systems or ductless air conditioners, offer several benefits for cooling indoor spaces. Here are some of the advantages of using an indoor A/C unit: Zoned Cooling: Ductless min

Read More