In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by John from Toronto on Twintech Heating and Cooling

Our furnace bit the dust, and Twintech came out to troubleshoot and diagnose the problem within a couple of hours. Mitch was super helpful, patient, and answered all of our questions. When we decided to get the furnace replaced, the crew was over first thing the next morning and did a fantastic job. Not only did they complete the job in a few hours, but they cleaned up and respected our house as they went, and answered all of our follow-up questions. I've used Twintech for our HVAC needs in the past and will continue to do so. I'd recommend them to anyone, and it feels good to support a local, family-owned business.

by Ryan k on Twintech Heating and Cooling

Dave and the Twintech team were fabulous from day 1 and helped us through the process to identifying a new furnace and AC unit. This was our first time through this process and Dave did a thorough job explaining all the components and was very patience answering all our questions. Dave provided great insights and fair pricing.

The Twintech team did an awesome installation. Very clean and efficient. I would highly recommended their service.

by Louise in Scarborough on Twintech Heating and Cooling

We had a new Amana furnace installed by Twintech and we were very pleased with the installation. It is nice to have a warm house again.

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Why Won't My Furnace Heat Up My House?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 26, 2023

There could be several reasons why your furnace is not heating up your house properly. Here are some common troubleshooting steps to help you identify and potentially fix the issue: Thermostat Settings: Check if your thermostat is set to the

Read More

What Are the Different Kinds of Heat Pumps?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 31, 2023

Heat pumps are devices that transfer heat from one place to another, typically from a lower-temperature space to a higher-temperature one. There are several types of heat pumps, each designed for specific applications and environmental conditions. Th

Read More

Why is My Panasonic Heat Pump Leaking?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 22, 2023

A Panasonic heat pump leaking water can be attributed to several potential issues. Here are some common reasons why a heat pump might be leaking: Condensate Drain Blockage: Heat pumps produce condensate as a byproduct of the heating and cool

Read More

How do Water Heaters Work?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 9, 2019

Have you ever wondered how a water heater works How does it heat the water in your home and make your showers warm At Twintech Heating & Cooling, we carry two types of water heaters: tank and tankless heaters.A tank water heater works by collec

Read More