CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by RJW in Ajax on Twintech Heating and Cooling

Thanks to the guys at Twintech Heating for a great job installing a new hot water tank. They set a time and day to remove the old tank and install the new one. They were on time and had the work done quickly and cleaned up after they were finished. Excellent work and great value.

by Marilyn in Milton on Twintech Heating and Cooling

In November, we contacted Twintech for a quote on a high efficiency furnace plus installation. Dave, the sales representative for the company was very friendly and informative. Upon arrival at our home, he willingly showed us his company licenses, clearly explained the operation of a high efficiency furnace and answered all our questions to our satisfaction. As well, Dave was the only sales representative that we contacted that was willing to make the arrangements for an energy audit. For us, this was a big plus as we found the government rebate program somewhat confusing to navigate. The furnace was installed on the date that was arranged in an efficient and professional manner by Greg (the owner) and Peter. Both men worked diligently, throughout a long day to complete the job and upon finishing, left the job site immaculate. When a neighbour raised concerns about the furnace venting location, Greg located an alternative location and resolved the situation with diplomacy. We chose the Napoleon furnace for its excellent warrant;y on the heat exchanger and because it was made in Canada! In addition, to the furnace warranty, Twintech offered us a 5 year warranty on labour which speaks to the quality and pride this team has in their workmanship. It has been over a month now (with some of the coldest January days on record) since we have had the furnace installed. The furnace runs quietly and distributes heat more evenly throughout our 90 year old Toronto home. We can't speak highly enough of the Twintech team and are very satisfied with their workmanship and job ethics. We have no hesitation about recommending them.

by Barry in Toronto on Twintech Heating and Cooling

What more could you ask for! Grant and Greg Dainty provided a professional,diligent and thorough approach to the installation of my furnace. I would highly recommend there services.

by Hector in Scarborough on Twintech Heating and Cooling

Last week our Furnace failed overnight. We called Twintech to help us get it running again. They did a really thorough check on it, and got it running in less than an hour. Given that it was an old Furnace (+20 years old), we were giving two options: repair it or replace it. Instead of doing a repair on it that could break in a week or two, they recommended us to change it. I like that they were honest on the recommendation, not forcing a new furnace on us. At the end we went with a new Furnace. Twintech solutions service & salesman gave us recommendation on the size of the unit and many options that could work for our home. They ended up doing an excellent work in our furnace, replacing the filter to a better option and replacing some pieces that had water damage. They cleaned after themselves and leave everything even better than what they found. They even went far and beyond tiding up the hose connections that we had on the basement.

by Ryan Doherty in Whitby on Twintech Heating and Cooling

I am in the process of finishing my basement and wanted to make sure I got the low hanging duct work fixed in advance. After reviewing 5 quotes I selected Twintech to award the contract to. The price was competitive however what won me over was Grant's (co-owner) attention to detail and his ability to focus on what my goals and priorities were for the project. His team completed the job over 3 days as there was significant duct work changes and the relocation of all of the equipment. They also completed the job with little downtime so we weren't left overnight without heat during freezing winter temperatures.

by Private User from Oshawa on Twintech Heating and Cooling

My father woke up to no heat one Saturday morning. We had a few names that friends had recommended but while checking out the companies' ratings on HomeStars, we found Twintech with great ratings too. The other companies either didn't get back to us or didn't have time to come at such short notice. TwinTech made the time in their schedule for what they judged to be an emergency: no heat in the home of an elderly person. At no extra fee for a short notice, weekend visit. They recommended an upgraded furnace unit and explained that we would qualify for a rebate that would bring the price down to that of a lower model. They set us up with the rep from the MNR that covers the rebate so that we didn't have to deal with the paperwork & phone calls ourselves. Installation was quick, efficient, & smooth. We were so pleased with their service we ordered a new water heater too. Both are working great (efficient & quiet!) & my father is safe & comfortable. We can't say enough about how pleased we are with their service. We have already recommended them to others.

by joe calabro in Pickering on Twintech Heating and Cooling

Twintech Heating & Cooling. I just want to say thanks for helping me . My Furnace stopped working. And l phone Dave Getgley he set me up with Greg. What an amazing team they did a great job in setting me up with a new Furnace. Anyone that needed a new Furnace these are the guys to call. Thanks again for a job well done.

by Peter from Ajax on Twintech Heating and Cooling

Our home has had poor heating and air conditioning the past couple of years. Dave recommended a Goodman solution with more power than we had. Grant and Greg installed the units in late November. Heating is better than ever. We have a warm home again and look forward to the winter. Can't wait to see how the AC runs in 2018. Job was super clean and professionally done. Highly recommended.

by iqster in Toronto on Twintech Heating and Cooling

Received a new range and needed someone to disconnect the old range and connect the new gas range. They did a thorough job and were kind enough to remove the old range from the house. Thank you!

by AJM in Pickering on Twintech Heating and Cooling

Very satisfied with this company! Salesperson Dave was very good, very knowledgeable and gave me the impression that he wanted to sell me what I needed rather than what would put the most money in the company's pocket. He also called back after the installation to see if I was satisfied with the result. The installation crew of Greg, Grant and Peter did a great job. They arrived on time, completed the job quickly, answered all my questions and thoroughly cleaned up. They told me to call if I had any further questions. They left me with the impression that they really cared about their work and my satisfaction and that it wasn't " just a job". Prior to researching for a new furnace, I had never heard of this company but I'm glad that I did and would highly recommend them to anyone looking for a new furnace or air conditioning unit. They may be small but they do a great job!!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

My AC keeps going out because the safety switch keeps tripping

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 31, 2023

My ac keeps turning off because what I believe is the safety switch keeps tripping, anytime I take the switch float off it kicks on within a few minuets and there is water where the float sits (like a lot of water) I can see I'll need to probably

Read More

Why Exhaust Fans Are Essential in Homes

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 7, 2018

Having exhaust fans in your home is beneficial for maintaining ideal air quality and temperature. Bathroom, kitchen, or whole systems improve ventilation as they let out the bad air to better a home’s interior environment. Check out how exhaus

Read More

Is My Air Conditioner Miswired?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 16, 2024

If you suspect your air conditioner is miswired, it could lead to improper functioning, electrical issues, or potential damage. Here are some signs that your air conditioner might be miswired: 1. Unit Not Turning On Issue: If your air condit

Read More

Why Should I Change My Air Filter?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 22, 2020

Your furnace and air conditioner work hard to keep your home comfortable during the cold and warm seasons. During these seasons, you should be checking your filter every 30 days and changing the filters at least every three months, depending on how o

Read More