CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by rcnichols electric in Whitby on Twintech Heating and Cooling

We had Grant and Greg Dainty quote to replace our 20 yr old furnace. I have known them for years and have had other jobs done by them ( AC and Pool Htr). The price was very reasonable and the job was completed in one day.

by Rick. F. in Pickering on Twintech Heating and Cooling

TwinTech was the right choice. Our consultation with Dave set the tone. Professional and knowledgeable, we even received a follow-up call within hours of our install completion, wow! TwinTech arrived as scheduled to install our A/C unit. Within minutes of arrival Greg noted and explained a few out of code faults on our furnace installed by another company, problems fixed, thanks TwinTech. Greg, Grant and "Subaru" Pete were meticulous start to finish. Highly recommended!

by Taresh, Pickering on Twintech Heating and Cooling

Twintech replaced our aging +20 yrs old Furnace & AC with the variable high efficiency Napoleon Furnace matched with the Goodman AC. Sales guy ,Dave was great, gave a no pressure estimate, explained about the Government Rebate program which they took care of completely including arranging the home energy audit. On the scheduled day Greg and his team arrived on time, did a great job and completed the same day , extremely professional and courteous, cleaned up everything , tested the system, Greg took his time to explain the setup. Very impressed with the Napoleon Furnace 9600 which did a great job in maintaining a comfortable temperature last winter and now with the hot weather the Goodman AC cooled the house in much less time than the old AC unit could ever. From start to finish Twintech were great and have no hesitation in recommending them 100%.

by Private User Pickering, ON on Twintech Heating and Cooling

The Twintech team did an excellent job installing our new Goodman air conditioner. They were polite and professional. Greg was knowledgeable and clearly experienced. Thank you Twintech for bringing our cooling system up to current regulations. Job well done!

by Y. M. from Pickering on Twintech Heating and Cooling

Dave from TwinTech was very knowledgeable, professional and thorough in the buying process. He helped us to identify the best furnace for our home and our budget. When we needed a new filter a year later and seemed to have a problem finding the right one, I called Dave up and he delivered a filter to me the next day! The cost was on par with other retailers, but it was this unexpected personal service that really was impressive. The furnace? Works like a charm.

by JLH from Pickering on Twintech Heating and Cooling

Imagine, it's 5 minutes after the midnight countdown New Year's eve and the furnace quits. We called TwinTech fully expecting to leave a message and actually spoke with Greg, one of the owners! We had an immediate repair early the next morning & a new furnace within the week. We have entrusted TwinTech with all our home HVAC service needs for over 6 years. That's why this week with an opportunity to purchase a new BBQ, we called them 1st to see about a gas line install. It's chicken on the grill tonight! They are efficient, reliable, honest, hard working, and -- attentive is an understatement.

by Curtis, Ajax on Twintech Heating and Cooling

Wonderful customer service, starting from the job quote (Dave), to the clean install, to the follow-up. Twintech is a small company which installed my Napoleon furnace, A/C, John Wood tank, and ran the line for my gas dryer. The installation was completed as promised in one day. The work area was kept very clean, and they even took care of my old rental tank. The professionalism and wonderful customer service is second to none. They completed all of my rebate paperwork, and now I'm getting $2000 back! You will not be disappointed if you hire this company for your project.

by Roy in Pickering on Twintech Heating and Cooling

I was referred to Twintech by a neighbour and was not disappointed. Not only was the customer service excellent their workmanship was second to none. Greg and Grant work extremely clean covering the pathway to the furnace room, labeling the essential parts, left the area spotless and were efficient. They cleaned up the mess left by the previous installers (wiring, improperly installed AC coil, and gaps in venting etc). They also ran through the operation of the new furnace and gave me some maintenance tips. Greg and Grant are professional and all around good guys. I will definitely recommend their service to anyone without hesitation.

by Peter Buck, Pickering on Twintech Heating and Cooling

Very satisfied with service from Twintech , beginning with all the information provided by Dave , which helped make the decision much easier . Installation was very smooth & done on time as promised & cleanup was well done . Would definitely recommend this company & use them again for any future needs . Well done.

by Angela from Ajax on Twintech Heating and Cooling

Twintech Heating & Cooling Inc. came in and replaced my 39 year old furnace with a beautiful Napoleon variable high efficiency furnace! Their work was efficient and professional and they were a pleasure to deal with, from sales to installation! I would highly recommend them.