CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Nancy H. from Oshawa on Twintech Heating and Cooling

Work was performed in a clean and timely manner. The furnace and metal work was performed by the Twintech team (did not require separate contractor to do the metal work). Energy audit was arranged and promised rebates were received. The overall price was very competitive. We have recommended Twintech to several of our friends and family. Awesome job.

by Syd from Whitby on Twintech Heating and Cooling

Grant and Greg installed a heating and AC system in our new Linwood post and beam home. Post and beam can be challenging structures for running ductwork and their high ceilings and open concept frequently frustrate efforts at balancing air flow and controlling temperatures. But these guys did it and did it right the first time. Even the building inspector was impressed with what he saw. More importantly, the boys brought a high degree of trust and integrity to the job. Something in short supply these days.

by jenner iksmom from Oshawa on Twintech Heating and Cooling

Very polite and professional. They removed my o
ld furnace and A/C and installed my new ones. They were efficient and thoroughly cleaned up when they were done! I would highly recommend them!

by Rob from Toronto on Twintech Heating and Cooling

Pro from start to finish. They were able to fix my gas fireplace at very little cost as well.

by murray mcmichael from Ajax on Twintech Heating and Cooling

Excellent installation very knowledgeable gentlemen! Would highly recommend them to all my friends for any hvac work !

by Private User from Private User on Twintech Heating and Cooling

I have used Twintech many times over the years. They always arrive quickly and get the issue fixed. The most recent incident was when my air conditioner broke last week I called Greg at 11:30am and he was at my home by 2:30pm he had the unit fixed by 3:30pm. Twintech are very reliable and honest and they are experts in the field. I have already recommended them to many of my friends. I would not use anyone but them for my heating and air conditioning issues.

by Kate A in Pickering on Twintech Heating and Cooling

I would highly recommend these guys, professional, fast and competitive pricing. I moved into this place with no working AC unit with a 8 month baby, he was able to come with in a week to fix even in the busy summer days. He really values his customers , I am already recommending to my neighbors.

by Private User in Whitby on Twintech Heating and Cooling

Very impressed they arrive to quote even though I had forgotten to call them back to confirm date & time. They showed the day before installation to deliver the unit. Returned the next day as promised at 9am. Project was completed in a professional manner. They even fixed a few things that they noticed were not installed correctly, or to code by previous heating & air contractors we had at our residence before. Would recommend this company to everyone!

by Private User from Bowmanville on Twintech Heating and Cooling

Greg removed old oil furnace and oil tank from basement relocated new Napoleon propane furnace to allow duct work to be rerouted to a much more suitable location. Moved air conditioner to the new furnace. Dave recommended two available grants to assist with cost. They kept to their original quoted price which was substantially lower than a competitors for the same furnace and work. They completed the work as stated when stated and left the area clean and tidy. We are very pleased with the outcome.

by astephenson in Oshawa on Twintech Heating and Cooling

Twintech installed a Goodman furnace and ac init. Very professional install, both units are working well.