CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by John from Toronto on Twintech Heating and Cooling

Our furnace bit the dust, and Twintech came out to troubleshoot and diagnose the problem within a couple of hours. Mitch was super helpful, patient, and answered all of our questions. When we decided to get the furnace replaced, the crew was over first thing the next morning and did a fantastic job. Not only did they complete the job in a few hours, but they cleaned up and respected our house as they went, and answered all of our follow-up questions. I've used Twintech for our HVAC needs in the past and will continue to do so. I'd recommend them to anyone, and it feels good to support a local, family-owned business.

by Ryan k on Twintech Heating and Cooling

Dave and the Twintech team were fabulous from day 1 and helped us through the process to identifying a new furnace and AC unit. This was our first time through this process and Dave did a thorough job explaining all the components and was very patience answering all our questions. Dave provided great insights and fair pricing.

The Twintech team did an awesome installation. Very clean and efficient. I would highly recommended their service.

by Louise in Scarborough on Twintech Heating and Cooling

We had a new Amana furnace installed by Twintech and we were very pleased with the installation. It is nice to have a warm house again.

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Avoiding HVAC Disasters - How It Can Be Done

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - June 14, 2018

Keeping your HVAC system in tiptop shape is key in averting high-priced conundrums in the future. Most homeowners overlook their own HVAC system and just start to listen when something goes wrong. This should not be the case. After all, you

Read More

Why is My AC Being So Loud?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 3, 2024

A loud air conditioning unit can be caused by various factors. Here are some common reasons why your AC might be noisy: Dirty or Clogged Filters: Accumulated dirt and debris in the filters can obstruct airflow, causing the unit to work harde

Read More

Why is Mold Growing on My Heat Pump?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 25, 2023

Mold growth on a heat pump can occur due to various factors, and it's essential to address the issue promptly as mold can negatively affect indoor air quality and the efficiency of your heat pump. Here are some common reasons why mold might be gr

Read More

Choosing the Perfect AC Unit

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 30, 2024

Choosing the perfect air conditioning (AC) unit involves considering several factors to ensure you select a system that efficiently cools your space, is cost-effective, and meets your specific needs. Here are key considerations to help you make th

Read More