Each of the following status codes is a two digit number with the first digit determined by number of flashes of the yellow led and the second digit determined by number of flashes of the green led.


Like many furnace manufacturers, Bryant uses flashing LED lights to indicate error codes that can give you an idea of what's wrong with your furnace when it's not functioning properly. The short flashes indicate the first digit of the two-digit code, and the long flashes indicate the second digit. Here's are some common error codes.


CODE: RED LED1 ON.
RESULT: Furnace is operating in emergency heat.

CODE: RED LED2 ON.
RESULT: The microprocessor has malfunctioned. To reset: Put setup switch "SW-1" in the "ON" position nad jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously with the door switch pushed in and power to the unit "ON". Disconnect jumper and place setup switch in the "OFF" position. If LED2 reappears, replace main control board.

CODE: YELLOW LED3 ON.
RESULT: Furnace is operating in high heat.

CODE: GREEN LED4 ON.
RESULT: Furnace is operating in low heat.

CODE: RED LED2 FLASHING.
RESULT: Line voltage polarity is reversed.

CODE: 1-1.
RESULT: NO FAULT IN RECENT HISTORY DISPLAY
FIX: Indicates no faults have occurred within the last five cycles. To read recent fault history, put setup switch "SW-1" in the "ON" position. To clear recent fault history, put setup switch "SW-1" in the "ON" position and jumper thermostat terminals "R", "W/W1" and "Y/Y2" simultaneously until an "11" is flashed.

CODE: 1-2.
RESULT: BLOWER CALIBRATION LOCKOUT
FIX: Indicates RPM calculated for low heat was less than 250 RPM or greater than 1300 RPM on two successive attempts. Auto reset after three hours. Reset power and refer to fault #44 section.

CODE: 1-3.
RESULT: LIMIT SWITCH LOCKOUT
FIX: Indicates the occurrence of 10 successive limit trips during high heat or three successive limit trips during low heat. Auto reset after three hours. Check for *Improper or misaligned limit and/or limit shield. *Improper high or low heat gas input adjustment. *Stuck high heat solenoid in gas valve.

CODE: 1-4.
RESULT: IGNITION LOCKOUT
FIX: Control will auto-reset after three hours.

CODE: 2-1.
RESULT: INVALID MODEL SELECTION
FIX: Indicates model plug is missing or incorrect. See wiring diagram for correct connector jumper location.

CODE: 2-2.
RESULT: SETUP ERROR
FIX: Indicates setup switch "SW-1" or "SW-6" is positioned improperly. The following combinations will cause the fault: *Thermostat call with "SW-1" "ON", or Thermostat call with "SW-6" "ON", or "SW-1" and "SW-6" both "ON" together.

CODE: 2-3.
RESULT: INVALID BLOWER AIRFLOW SELECTION
FIX: Indicates improper "A/C" or "CF" switch setting. The 042 and 14 units can deliver 1-1/2 to 3-1/2 tons A/C and 600 to 1400 CFM for continuous fan. The 060 and 20 unit can deliver 2 to 5 tons A/C and 800 to 2000 CFM for continuous fan. If code is flashing, unit will default tp closest allowable airflow.

CODE: 2-4.
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: - Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1.
RESULT: PRESSURE SWITCH DID NOT CLOSE OR REOPENED
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Excessive wind - Proper vent sizing -- Defective inducer motor - Low inducer voltage (115VAC) - Defective pressure switch -Inadequate combustion air supply - Restricted vent - Disconnected or obstructed pressure tubing - Low inlet gas pressure (if LGPS used) If it opens during blower ondelay period, blower will come on for the selected blower off-delay.

CODE: 3-3.
RESULT: LIMIT CIRCUIT FAULT
FIX: Indicates a limit, or flame rollout is open. Blower will run for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts of Flame rollout switch requires manual reset. Check for: - Restricted vent - Proper vent sizing - Loose blower wheel - Excessive wind - Dirty filter or restricted duct system. - Defective blower motor or capacitor. - Defective switch or connections. - Inadequate combustion air supply (Flame Roll-out Switch open).

CODE: 3-4.
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for the selected blower off-delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green/Yellow wire MUST be connected to furnace sheet metal.

CODE: 4-1.
RESULT: BLOWER OUTSIDE VALID SPEED RANGE
FIX: Indicates the blower is not operating at the calculated RPM. If this fault occurs in conjunction with fault #44 check wiring to motor otherwise refer to the trouble-shooting guide.

CODE: 4-2.
RESULT: INDUCER OUTSIDE VALID SPEED RANGE
FIX: Indicates the inducer is not operating at the calculated RPM. Or it has not started within 10 seconds after a call for heat. Check wiring to motor otherwise refer to the troubleshooting guide.

CODE: 4-3.
RESULT: PRESSURE SWITCH CALIBRATION FAULT
FIX: Indicates the low and high pressure switch "make" points during high heat purge are not within calibration range. Check for: -Plugged condensate drain Water in vent piping, possibly sagging pipe -Improper pressure switch wiring or pressure switch tubing connections -Failed or "out of calibration" pressure switches.

CODE: 4-4.
RESULT: BLOWER CALIBRATION FAULT
FIX: Indicates the calculated blower speed is below 250 or above 1300 RPM. Unit will default to low or high heat mode if possible. If this fault occurs in conjunection with fault #41, check wiring to motor otherwise refer to the trouble shooting guide. If this fault occurs by itself, check for undersized ductwork, or excessive static caused by a dirty filter, or closed registers.

CODE: 4-5.
RESULT: CONTROL CIRCUITRY LOCKOUT
FIX: Auto-reset after one hour lockout due to; - Gas valve relay stuck open - Flame sense circuit failure - Software check error Reset power to clear lockout. Replace control if status code repeats.


See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

by Trevor Owens on Twintech Heating and Cooling

I returned from vacation to find my AC unit on the Fritz. After calling way too many places I connected with TwinTech. I’ve used the company in the past for my furnace so I was happy when I recognized Greg at my front door. He’s great and the service is always top notch. I’d highly recommend using twintech for honest, superior service in the Durham region. Thanks!

by Nicole Alain on Twintech Heating and Cooling

I called Twin Tech when my air conditioning stopped working. Greg came over to diagnose the issue - the same day. He was able to diagnose the issue and resolve it quite quickly. Although it was a quick fix, Greg was very thorough in explaining the issue and provided great advice. Not to mention, I felt very comfortable having Greg in my home - which I consider very important when hiring a service provider. Twin Tech will be my go-to from now on. Thank you!!

by Courtney Parkes on Twintech Heating and Cooling

Just hired TwinTech Heating & Cooling to do an A/C Unit removal & reinstall to allow for landscaping access on the side of my house, and they were wonderful!
Bob, Greg & Mitch make a great team! Quick appointment times, super knowledgeable, expert troubleshooting capabilities & very customer service oriented.
I would highly recommend them for all of your HVAC needs! Great job guys!!

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Is My Amana Heat Pump Good For the Environment?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - January 30, 2024

I can provide some general information that might help you evaluate the environmental impact of your Amana heat pump. Energy Efficiency: Heat pumps, including those made by Amana, are generally more energy-efficient than traditional heating

Read More

Panasonic Heat Pump Service Durham Region

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 21, 2025

When it comes to efficient home climate control, few solutions match the reliability and innovation of Panasonic heat pumps. Whether you're aiming to reduce your energy bills or looking for an eco-friendly way to heat and cool your home, Panas

Read More

Common Furnace Problems and How to Fix Them

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 26, 2024

Here’s a comprehensive guide to common furnace problems and how to fix them: 1. Furnace Won’t Turn On Possible Causes: Thermostat is not set correctly. Power issue (tripped circuit breaker or blown fuse). Pilot light is

Read More

How does the AC get billed?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 23, 2023

I just moved in with my best friend and we are confused on how the AC will be determined how much it costs us. We are currently going through a 110° heatwave where we live. The issue IS NOT what the temperature is set at, I grew up without

Read More