In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

by Jaime-Lynne in Pickering on Twintech Heating and Cooling

Greg came over at 9:30pm to rescue my daughter and I from a horrible experience with Enercare that evening. He was professional. Kind. And got us what we needed quickly and at an afford price. I would 100% recommend calling on Greg and his team for any of your heating and cooling needs in the future!!

by Matt C. Oshawa on Twintech Heating and Cooling

Installed a great hot water heater when our old one failed. When my furnace died during cold weather they showed up quickly and my house was warm before my wife got home. :)

by B Davis in Pickering on Twintech Heating and Cooling

I don’t usually right reviews but when you receive service like this I felt it was a must. Honest and fair. I Have 4 children and on Xmas eve my furnace stopped working and a gentleman came out and got me up and running so at least we would have heat for the holidays. As promised he would replace my furnace early in the new year. The job was completed on time, great price for quality furnace and extremely clean and professional job. Would have never known anyone was in the house. Not a spec of dust or mess from lugging out an old rusty furnace. If you have any ac or heating concerns twintech is your only option. I was royally impressed with and I’m sure you will be too.

by stan.marosek from Ajax on Twintech Heating and Cooling

Class Act ! These guys were professional right from the quote stage through to installation. They know their stuff and took their time to help educate me. They take pride in their work and it shows. I would recommend TwinTech Heating and Cooling to anyone. Keep up the great work !!!

by W. Lacombe in Pickering on Twintech Heating and Cooling

This Company is terrific. No high pressure sales and they deliver exactly what they promise to deliver. The new furnace is great and we now get consistent temperatures throughout the house. The installers were great and very efficient and completed the work on schedule on the promised day. Everyone representing this company was very aware of their presence in our house and worked diligently to keep our home as uninterrupted and as clean as was humanly possible. We did not need to go around the house to clean up after they left, what a nice surprise. We have had follow up by the company to ensure everything is to our satisfaction. How unusual in today's environment. The impression left by Twintech is that they care about us and our home. This is so refreshing in today's high tech world. Out thanks go out to Dave in sales and G, G, and P (the installers).

by jiinyiong in Ajax on Twintech Heating and Cooling

They were Timely and professional. They were very Knowledgeable with answering all of my questions.

by Connie in Pickering on Twintech Heating and Cooling

The entire process was prompt and professional, from the initial quote to the installation of the new furnace. The team installed the new furnace and removed the old one in approx. 4 hrs. The guys were very knowledgeable and gave me lots of information. I have used Twintech before for a new A/C installation and new I was in good hands.

by Valentine in Pickering on Twintech Heating and Cooling

The overall experience dealing with this company was great from start to finish when getting a new furnace and ac this year. Everything was clearly explained to us during our consultation with Dave and there were no surprises with added costs. The work was done as expected and their response time to inquiries were very timely generally within a few hours or less. They are all very professional and was a pleasure to do business with them. Highly recommend to anyone looking for honest quality professional service.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Is My Air Conditioner Working?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - June 11, 2024

To determine if your air conditioner is working properly, you can follow these steps: 1. Check the Thermostat: Ensure that the thermostat is set to "cool" mode. Make sure the temperature setting is lower than the current room tem

Read More

Furnace Unit: Why Keep it Clean?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 11, 2025

Keeping your furnace unit clean is essential for maintaining efficiency, improving indoor air quality, and extending its lifespan. Here’s why regular cleaning is important: 1. Improved Efficiency Dust and debris buildup in your furnace ca

Read More

Is My Furnace Unit Prepared for the Season?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 5, 2024

To determine if your furnace is prepared for the season, it's important to go through a checklist that ensures it's functioning properly and efficiently. Here's a quick guide to help you evaluate whether your furnace is ready: 1. Check

Read More

Maximizing Your AC Units Efficiency

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 24, 2024

Maximizing your AC unit's efficiency can help you save on energy costs, improve comfort, and extend the lifespan of the system. Here are some practical tips to achieve this: Regular Maintenance Annual Professional Service: Schedule an an

Read More