CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by David from Toronto on Twintech Heating and Cooling

I first met Greg and Grant (The Twin Brothers from Twin Tech - yup -it's not just a cool company name) back in 2014 when our furnace broke down and they installed our Carrier Furnace and AC that we purchased through Sears. I liked them instantly when I met them due to their friendly and professional service, and the fact that they didn't mind taking a little extra time to explain things in terms I could understand. Since that time they have reached out to me at least once a year to ensure that everything was running smoothly with my system and to keep me appraised of their evolving services. Due to this high level of proactive customer service I didn't hesitate to call and obtain their help for a Gas Stove removal and installation. When I scheduled the call Greg and Grant let me know that they would arrive the morning of the appliance delivery to disconnect the old gas stove, and then return in the afternoon to connect the new stove. Sure enough, they did just that as promised. Where they exceeded my expectations is with the extra level of support helping to assemble the burners and grills on the stove and in the oven. This may seem like a small thing to some but to my wife who was at home during this entire process it meant a stress free transition to the meal prep for the day. When I called home to ask about the install she commented that, "they left the place cleaner than it was when they arrived and they setup all the grills on top of the stove and in the oven... they didn't have to do all that -Wow!". You know what they say, Happy Wife, Happy Life. So in summary, I am recommending Twintech Heating & Cooling for all of your Furnace, Air Conditioning, and Gas Line needs. I've even called on these guys to help swap out a leaky water valve. They are just so easy to reach and communicate with by phone, and they don't mind a text message to confirm the details. You can rest easy when you have the Twins on your side as an extension of your household maintenance plan.

by Jr in Pickering on Twintech Heating and Cooling

First thing, they actually showed up for a quote. Other big name companies in the area didn't even return my call , job was done as expected and new equipment is quiet and installed very clean and professional. Would highly recommend these guys.

by Melissa P. from Port Hope on Twintech Heating and Cooling

They removed our old furnace and replaced it with a new furnace and AC system.

by Nancy H. from Oshawa on Twintech Heating and Cooling

Work was performed in a clean and timely manner. The furnace and metal work was performed by the Twintech team (did not require separate contractor to do the metal work). Energy audit was arranged and promised rebates were received. The overall price was very competitive. We have recommended Twintech to several of our friends and family. Awesome job.

by Syd from Whitby on Twintech Heating and Cooling

Grant and Greg installed a heating and AC system in our new Linwood post and beam home. Post and beam can be challenging structures for running ductwork and their high ceilings and open concept frequently frustrate efforts at balancing air flow and controlling temperatures. But these guys did it and did it right the first time. Even the building inspector was impressed with what he saw. More importantly, the boys brought a high degree of trust and integrity to the job. Something in short supply these days.

by jenner iksmom from Oshawa on Twintech Heating and Cooling

Very polite and professional. They removed my o
ld furnace and A/C and installed my new ones. They were efficient and thoroughly cleaned up when they were done! I would highly recommend them!

by Rob from Toronto on Twintech Heating and Cooling

Pro from start to finish. They were able to fix my gas fireplace at very little cost as well.

by murray mcmichael from Ajax on Twintech Heating and Cooling

Excellent installation very knowledgeable gentlemen! Would highly recommend them to all my friends for any hvac work !

by Private User from Private User on Twintech Heating and Cooling

I have used Twintech many times over the years. They always arrive quickly and get the issue fixed. The most recent incident was when my air conditioner broke last week I called Greg at 11:30am and he was at my home by 2:30pm he had the unit fixed by 3:30pm. Twintech are very reliable and honest and they are experts in the field. I have already recommended them to many of my friends. I would not use anyone but them for my heating and air conditioning issues.

by Kate A in Pickering on Twintech Heating and Cooling

I would highly recommend these guys, professional, fast and competitive pricing. I moved into this place with no working AC unit with a 8 month baby, he was able to come with in a week to fix even in the busy summer days. He really values his customers , I am already recommending to my neighbors.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Amana Furnace Troubleshooting Tips

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 23, 2023

If you're experiencing issues with your Amana furnace, there are several troubleshooting tips you can try before calling a professional technician. Keep in mind that furnace troubleshooting can be complex, and if you are unsure or uncomfortable w

Read More

Why Did My Heat Pump Shut Off On Its Own?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 26, 2023

There could be several reasons why your heat pump shut off on its own. Some common reasons include: Thermostat Settings: Check your thermostat settings to ensure that the desired temperature is set correctly. If the temperature setti

Read More

Furnace: Dangers of Lack of Maintenance

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 16, 2024

Regular furnace maintenance is essential for the safety, efficiency, and longevity of your heating system. Neglecting maintenance can lead to various dangers that affect not only your comfort but also your health and home. Below are the primary risks

Read More

What are the best ways to save on energy costs?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 11, 2019

There is no denying that each year, our summers are getting warmer and winters are getting colder. For homeowners, the cost to heat or cool a home can be expensive. At Twintech, we have some helpful tips on how to save money on your next energy bill.

Read More