CODE: E105.
RESULT: Device communication problem - No other devices on RS BUS (Communicating systems only).
FIX: Equipment is unable to communicate indicates numerous message errors. In most cases errors are related to electrical noise. Make sure high voltage power is separated from RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor unit. Check for a high voltage source of noise close to the system. Fault clears after communication is restored.

CODE: E110.
RESULT: Low line voltage.
FIX: Line Voltage low (Voltage tower than nameplate rating). Check power line voltage and correct. Alarm clears 5 seconds after fault recovered.

CODE: E111.
RESULT: Line voltage polarity reversed.
FIX: Reverse line power voltage wiring. System resumes normal operation 5seconds after fault recovered.

CODE: E112.
RESULT: Ground not detected.
FIX: System shuts down. Provide proper earth ground. System resumes normal operation 5 seconds after fault recovered.

CODE: E113.
RESULT: High line voltage.
FIX: Line Voltage high (Voltage higher than nameplate rating). Provide power voltage within proper range. System resumes normal operation 5seconds after fault recovered.

CODE: E114.
RESULT: Line voltage frequency out of range.
FIX: No 60 Hertz power. Check voltage and line power frequency. Correct voltage and frequency problems. System resumes normal operation 5seconds after fault recovered.

CODE: E115.
RESULT: Low 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts). Check and correct voltage. Check for additional power robbing equipment connected to system. May require installation of larger VA transformer to be installed in furnace/air handler. Clears after fault recovered.

CODE: E116.
RESULT: High 24V.
FIX: 24 Volt Power high (Range is 18 to 30 Volts) Check and correct voltage. Check for proper line voltage (120V 240V etc) to equipment. Clears when control senses proper voltage.

CODE: E117.
RESULT: Poor ground detected (Warning only).
FIX: Provide proper grounding for unit. Check for proper earth ground to the system. Warming only will clear 30 seconds after fault recovered.

CODE: E120.
RESULT: Unresponsive device (Communicating systems only).
FIX: Usually caused by delay in outdoor unit responding to indoor unit poling. Recycle power. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.

CODE: E124.
RESULT: Active communicating thermostat signal missing for more than 3 minutes (Communicating systems only).
FIX: Equipment lost communication with the thermostat. Check four wiring connections, ohm wires, and cycle power at the thermostat. Alert stops all services and waits for heart beat message from thermostat (subnet controller). Cleared after valid thermostat (subnet) message is received.

CODE: E125.
RESULT: Control failed self check, internal error, failed hardware. Will restart if error recovers, Integrated control not communicating Covers hardware errors (flame sense circuit faults, pin shorts, etc).
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E126.
RESULT: Control internal communication problem.
FIX: Hardware problem on the control. Cycle power on control. Replace if problem prevents service and is persistent. Cleared 300 seconds after fault recovered.

CODE: E131.
RESULT: Corrupted control parameters (Verify configuration of system) (Communicating systems only).
FIX: Reconfigure the system. Replace control if heating or cooling is not available. Only applicable in the communicating mode not in startup. Exit from Commissioning and Execute Se+ factory Default mode. Control will still operate on default parameter settings.

CODE: E180.
RESULT: Outdoor air temperature sensor failure. Only shown if shorted or out of range (Communicating systems only).
FIX: Compare outdoor sensor resistance to temperature resistance chartsin unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s) If detected (reading in range), appropriate feature will be set as installed and that could be seen in 'About' screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configuration and make sure that temperature sensor is marked as not installed in indoor Unit 'About' screen. When indoor unit control is replaced thermostat will 'tell' new control if temperature sensor is in system or not. Clears 30 seconds after fault recovered.

CODE: E200.
RESULT: Hard Lock out - Rollout circuit open or previously open.
FIX: Correct cause of rollout trip or replace flame rollout switch. Test furnace operation. Cleared after fault recovered.

CODE: E201.
RESULT: Indoor blower/communication failure. Unable to communicate with blower motor.
FIX: Indoor blower communication failure including power outage. Lost communication with indoor blower motor. Possible causes: motor not powered, loose wiring. Problem may be on control or motor side. Cleared after fault recovered.

CODE: E202.
RESULT: Indoor blower motor mismatch - indoor motor horsepower does not match unit capacity.
FIX: Incorrect appliance capacity code selected. Check for proper configuring under Unit Size Code for Furnace/Air Hander on configuration guide or in installation instructions. Cleared after the correct match is detected following a reset. (Remove thermostat from system while applying power and reprogramming).

CODE: E203.
RESULT: Appliance capacity size is NOT programmed. Invalid unit codes. Refer to configuration flow chart.
FIX: No appliance capacity code selected. Check for proper configuring under Unit Size Codes for Furnace on configuration guide or in installation instruction. Critical Alert Cleared after valid unit code is read following a reset (remove thermostat from system while applying power and reprogramming).

CODE: E204.
RESULT: Gas valve mis-wired.
FIX: Check gas valve operation and wiring. Clears when repaired control.

CODE: E205.
RESULT: Gas valve control relay contact shorted.
FIX: Check wiring on control and gas valve. If wiring is correct replace control.

CODE: E206.
RESULT: Gas valve second stage relay failure.
FIX: Furnace will operate on 1st stage for remainder of the heating demand. Will clear after fault recovered. If unable to operate 2nd stage replace control.

CODE: E207.
RESULT: Hot surface igniter sensed open - Refer to troubleshooting.
FIX: Measure resistance of hot surface igniter. Replace if open or not within specified range found in 10M. Resumes normal operation after fault is cleared.

CODE: E223.
RESULT: Low pressure switch failed open.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E224.
RESULT: Low pressure switch failed closed. Refer to troubleshooting.
FIX: Check pressure (inches W.C) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

CODE: E225.
RESULT: High pressure switch failed open. Refer to troubleshooting.
FIX: Check pressure(inches W.C) of high pressure switch closing on heatcall. Measure operating pressure (inches w.c. Inspect vent and combustion air inducer for correct operation and restriction Resumes normal operation after fault is cleared.

CODE: E226.
RESULT: High pressure switch failed closed. Refer to troubleshooting.
FIX: Check operation of high pressure closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.


See What Our Customers Are Saying:

by Private User in Whitby on Twintech Heating and Cooling

Very impressed they arrive to quote even though I had forgotten to call them back to confirm date & time. They showed the day before installation to deliver the unit. Returned the next day as promised at 9am. Project was completed in a professional manner. They even fixed a few things that they noticed were not installed correctly, or to code by previous heating & air contractors we had at our residence before. Would recommend this company to everyone!

by Private User from Bowmanville on Twintech Heating and Cooling

Greg removed old oil furnace and oil tank from basement relocated new Napoleon propane furnace to allow duct work to be rerouted to a much more suitable location. Moved air conditioner to the new furnace. Dave recommended two available grants to assist with cost. They kept to their original quoted price which was substantially lower than a competitors for the same furnace and work. They completed the work as stated when stated and left the area clean and tidy. We are very pleased with the outcome.

by astephenson in Oshawa on Twintech Heating and Cooling

Twintech installed a Goodman furnace and ac init. Very professional install, both units are working well.

by rcnichols electric in Whitby on Twintech Heating and Cooling

We had Grant and Greg Dainty quote to replace our 20 yr old furnace. I have known them for years and have had other jobs done by them ( AC and Pool Htr). The price was very reasonable and the job was completed in one day.

by Rick. F. in Pickering on Twintech Heating and Cooling

TwinTech was the right choice. Our consultation with Dave set the tone. Professional and knowledgeable, we even received a follow-up call within hours of our install completion, wow! TwinTech arrived as scheduled to install our A/C unit. Within minutes of arrival Greg noted and explained a few out of code faults on our furnace installed by another company, problems fixed, thanks TwinTech. Greg, Grant and "Subaru" Pete were meticulous start to finish. Highly recommended!

by Taresh, Pickering on Twintech Heating and Cooling

Twintech replaced our aging +20 yrs old Furnace & AC with the variable high efficiency Napoleon Furnace matched with the Goodman AC. Sales guy ,Dave was great, gave a no pressure estimate, explained about the Government Rebate program which they took care of completely including arranging the home energy audit. On the scheduled day Greg and his team arrived on time, did a great job and completed the same day , extremely professional and courteous, cleaned up everything , tested the system, Greg took his time to explain the setup. Very impressed with the Napoleon Furnace 9600 which did a great job in maintaining a comfortable temperature last winter and now with the hot weather the Goodman AC cooled the house in much less time than the old AC unit could ever. From start to finish Twintech were great and have no hesitation in recommending them 100%.

by Private User Pickering, ON on Twintech Heating and Cooling

The Twintech team did an excellent job installing our new Goodman air conditioner. They were polite and professional. Greg was knowledgeable and clearly experienced. Thank you Twintech for bringing our cooling system up to current regulations. Job well done!

by Y. M. from Pickering on Twintech Heating and Cooling

Dave from TwinTech was very knowledgeable, professional and thorough in the buying process. He helped us to identify the best furnace for our home and our budget. When we needed a new filter a year later and seemed to have a problem finding the right one, I called Dave up and he delivered a filter to me the next day! The cost was on par with other retailers, but it was this unexpected personal service that really was impressive. The furnace? Works like a charm.

by JLH from Pickering on Twintech Heating and Cooling

Imagine, it's 5 minutes after the midnight countdown New Year's eve and the furnace quits. We called TwinTech fully expecting to leave a message and actually spoke with Greg, one of the owners! We had an immediate repair early the next morning & a new furnace within the week. We have entrusted TwinTech with all our home HVAC service needs for over 6 years. That's why this week with an opportunity to purchase a new BBQ, we called them 1st to see about a gas line install. It's chicken on the grill tonight! They are efficient, reliable, honest, hard working, and -- attentive is an understatement.

by Curtis, Ajax on Twintech Heating and Cooling

Wonderful customer service, starting from the job quote (Dave), to the clean install, to the follow-up. Twintech is a small company which installed my Napoleon furnace, A/C, John Wood tank, and ran the line for my gas dryer. The installation was completed as promised in one day. The work area was kept very clean, and they even took care of my old rental tank. The professionalism and wonderful customer service is second to none. They completed all of my rebate paperwork, and now I'm getting $2000 back! You will not be disappointed if you hire this company for your project.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Amana Furnace Troubleshooting Tips

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 23, 2023

If you're experiencing issues with your Amana furnace, there are several troubleshooting tips you can try before calling a professional technician. Keep in mind that furnace troubleshooting can be complex, and if you are unsure or uncomfortable w

Read More

Why Did My Heat Pump Shut Off On Its Own?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 26, 2023

There could be several reasons why your heat pump shut off on its own. Some common reasons include: Thermostat Settings: Check your thermostat settings to ensure that the desired temperature is set correctly. If the temperature setti

Read More

Furnace: Dangers of Lack of Maintenance

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 16, 2024

Regular furnace maintenance is essential for the safety, efficiency, and longevity of your heating system. Neglecting maintenance can lead to various dangers that affect not only your comfort but also your health and home. Below are the primary risks

Read More

What are the best ways to save on energy costs?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 11, 2019

There is no denying that each year, our summers are getting warmer and winters are getting colder. For homeowners, the cost to heat or cool a home can be expensive. At Twintech, we have some helpful tips on how to save money on your next energy bill.

Read More