The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Each of the following status codes is a two digit number with the first digit determined by number of flashes of the YELLOW L.E.D. and the second digit determined by number of flashes of the GREEN L.E.D.


If status code recall is needed, do not remove power or blower door. Briefly remove and then reconnect one main limit wire to display stored status code.


To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R" thermostat lead. Briefly short the TEST terminal to the "COM24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer motor will run for the entire component test. The hot surface ignitor, blower motor-heat speed and blower motor-cool speed will be turned ON for 10-15 seconds each. Gas Valve and humidifier will not be turned on.


CODE: CONTINUOUS OFF
RESULT: Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2

CODE: CONTINUOUS ON
RESULT: Control has 24VAC power

CODE: RAPID FLASHING
RESULT: Line voltage (115VAC) polarity reversed.
FIX: If twinned, refer to twinning kit instructions.

CODE: 1-1
RESULT: NO PREVIOUS CODE
FIX: Stored status codes are erased when power (115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.

CODE: 1-2
RESULT: BLOWER ON AFTER POWER UP (115VAC or 24VAC)
FIX: Blower runs for 90 seconds, if unit is powered up during a call for heat (R-W closed)

CODE: 1-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT
FIX: Control will auto reset after 3 hours. Reset switch or replace fuse link.

CODE: 1-4
RESULT: IGNITION LOCKOUT- Control will auto-reset after three hours.

CODE: 2-1
RESULT: GAS HEATINGING LOCKOUT
FIX: Control will NOT auto reset. Check for: *Mis-wired gas valve *Defective control (Valve relay)

CODE: 2-2
RESULT: ABNORMAL FLAME-PROVING SIGNAL
FIX: Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check for: *Leaky gas valve *Stuck open gas valve

CODE: 2-3
RESULT: PRESSURE SWITCH DID NOT OPEN
FIX: Check for: * Obstructed pressure switch *Pressure switch stuck.

CODE: 2-4
RESULT: SECONDARY VOLTAGE FUSE IS OPEN
FIX: Check for: *Short circuit in secondary voltage (24VAC) wiring.

CODE: 3-1
RESULT: PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT SWITCH (when used*) OR BLOCKED VENT SWITCH (when used) DID NOT CLOSE OR REOPENED (DOWNFLOW ONLY)
FIX: If open longer than five minutes, inducer shuts off for 15 minutes before retry. Check for: - Proper vent sizing - Defective inducer motor - Low inducer voltage (115VAC) - Defective blower motor or capacitor - Restricted vent - Excessive wind - Defective pressure switch - Inadequate combustion air supply - Disconnected or obstructed pressure tubing If it opens after trial for ignition period, blower will come on for 90 second recycle delay,

CODE: 3-3
RESULT: LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN
FIX: If open longer than 3 minutes, code changes to lockout #13. Flame roll-out switch requires manual reset. Check for: - Defective blower motor or capacitor - Dirty filter or restricted duct system - Loose blower wheel - Defective switch or connections - Inadequate combustion air supply (Flame roll-out switch or fuse link open) - Open Flame Roll-out Switch or fuse link. Manual reset or replace.

CODE: 3-4
RESULT: IGNITION PROVING FAILURE
FIX: Control will try three more times before lockout #14 occurs. If flame signal lost during blower on-delay period, blower will come on for 90 second recycle delay. Check for: - Control ground continuity - Flame sensor must not be grounded - Oxide buildup on flame sensor (clean with fine steel wool) - Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal). - Gas valve defective or gas valve turned off - Manual valve shut-off - Defective Hot Surface Ignitor - Low inlet gas pressure - Inadequate flame carryover or rough ignition - Green wire MUST be connected to furnace sheet metal.


See What Our Customers Are Saying:

by John from Toronto on Twintech Heating and Cooling

Our furnace bit the dust, and Twintech came out to troubleshoot and diagnose the problem within a couple of hours. Mitch was super helpful, patient, and answered all of our questions. When we decided to get the furnace replaced, the crew was over first thing the next morning and did a fantastic job. Not only did they complete the job in a few hours, but they cleaned up and respected our house as they went, and answered all of our follow-up questions. I've used Twintech for our HVAC needs in the past and will continue to do so. I'd recommend them to anyone, and it feels good to support a local, family-owned business.

by Ryan k on Twintech Heating and Cooling

Dave and the Twintech team were fabulous from day 1 and helped us through the process to identifying a new furnace and AC unit. This was our first time through this process and Dave did a thorough job explaining all the components and was very patience answering all our questions. Dave provided great insights and fair pricing.

The Twintech team did an awesome installation. Very clean and efficient. I would highly recommended their service.

by Louise in Scarborough on Twintech Heating and Cooling

We had a new Amana furnace installed by Twintech and we were very pleased with the installation. It is nice to have a warm house again.

by Private User on Twintech Heating and Cooling

Excellent job. Excellent service. Competitive price. Its rare to find a company with the knowledge and professional results we have experienced with Twintech. The clean and neat installation with attention to detail and drop sheers to respect our property is a clear indication of Twintechs high level of integrity. The 1-1/2 gas line upgrade they did for our pool 3 years ago was awesome. Can't say enough. Thank-you Twintech.

by Private User on Twintech Heating and Cooling

Twitch did a great job with the installation of our new furnace. I really appreciated their honesty and I could trust what they were telling me. Another company tried to suggest significantly more work at a greater cost claiming it was necessary to meet current building code. Twintech is very fair. All staff I meet were friendly, polite and trustworthy. I would recommend Twitch for a furnace.

by Private User on Twintech Heating and Cooling

This is a professional team that's easy to deal with. I would strongly recommend them

by hj.taggart in OSHAWA on Twintech Heating and Cooling

Very professional firm from start to finish!
They removed the old oil tank and furnace. They installed air conditioning and a new propane furnace.
Professional installation, on time and no mess.
Very pleased with their work and would highly recommend the company. Our house is three stories so they spent the time to do all the calculations to make sure we would have great performance on each floor.
Thank you again!

by susieschoeppler in Oshawa on Twintech Heating and Cooling

Upon a routine yearly maintenance, it was discovered there was a leak in the heat exchanger and a I needed a new furnace. I know nothing about these things and was completely stressed out. The company I had the maintenance plan with quoted me a huge number to rent a furnace, I just wanted to cry. Then I spoke to Dave at Twintech. He was so knowledgeable and calming, provided me a fair quote and within a few days I had an amazing crew show up to my house and install my new energy efficient furnace! I have already recommended these wonderful people at Twintech to a good friend of mine. Thank you Twintech!!

by Private User on Twintech Heating and Cooling

Great service and great people to deal with, from sales to installer. I highly recommend this company.

by GR from Oshawa on Twintech Heating and Cooling

Twintech replaced our aging furnace and air conditioner recently. I highly recommend this company. Their quote was competitive, they were on time and respectful of our home and extremely professional. From the salesman to the installers and the owner who followed up afterward to ensure we were satisfied, we are very pleased with the service. We are looking forward to working with this company for all of our HVAC needs for the years to come. Excellent workmanship and service!

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Why Won't My Furnace Heat Up My House?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 26, 2023

There could be several reasons why your furnace is not heating up your house properly. Here are some common troubleshooting steps to help you identify and potentially fix the issue: Thermostat Settings: Check if your thermostat is set to the

Read More

What Are the Different Kinds of Heat Pumps?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 31, 2023

Heat pumps are devices that transfer heat from one place to another, typically from a lower-temperature space to a higher-temperature one. There are several types of heat pumps, each designed for specific applications and environmental conditions. Th

Read More

Why is My Panasonic Heat Pump Leaking?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 22, 2023

A Panasonic heat pump leaking water can be attributed to several potential issues. Here are some common reasons why a heat pump might be leaking: Condensate Drain Blockage: Heat pumps produce condensate as a byproduct of the heating and cool

Read More

How do Water Heaters Work?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 9, 2019

Have you ever wondered how a water heater works How does it heat the water in your home and make your showers warm At Twintech Heating & Cooling, we carry two types of water heaters: tank and tankless heaters.A tank water heater works by collec

Read More