In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Robert, Pickering on Twintech Heating and Cooling

Had new furnace installed and ran into some difficulties but the contractor responded in a timely and efficient manner - after further service calls were made, a reasonable resolution was found.

by Brian Burns, Whitby on Twintech Heating and Cooling

The work was done quickly efficiently neatly and professionally. Pleased with the service, information, product, and the company.

by Geoff, Port Perry on Twintech Heating and Cooling

Great sales member named Dave came in told us some amazing items and how they would be priced installed an all. We couldn’t believe it! The next day the ac was installed, that day one employee named Greg told us that our furnace was working way to hard and was causing us to use way too much gas. So two days later they came in an installed a new furnace!

by MB, Ajax on Twintech Heating and Cooling

Installation was done quickly and professionally. The new furnace is quiet and provides even heat.

by Richard from Oshawa on Twintech Heating and Cooling

They removed and discarded old furnace. Installed new furnace. Installed air intake pipe, that had never been installed by builder, no charge. Replaced loose hose on floor with hard pipe and rerouted it to drain, no charge. Almost 33% cheaper then quote from Enercare, which was the company we dealt with and had insurance with for 8 years. No yearly fee for cleaning/insurance, saves 300 a year. Courteous, professional, fast, and friendly. My wife and I have been recommending them to everyone we know and meet, and will continue to do so. Thanks for everything, Twintech!!!

by Darcy from Pickering on Twintech Heating and Cooling

This company was great to deal with. Our furnace went down and they installed a new furnace the next day with a lot of professionalism!

by gillian hooton from Uxbridge on Twintech Heating and Cooling

Finally! An honest company with highly knowledgeable and informative staff. Had a furnace service and found multiply errors in our system from an amateur installer. Very fair price to correct problems and will definitely use again.

by dflynn in Ajax on Twintech Heating and Cooling

Had to replace the heating & a/c unit in a condo apartment dwelling. this company recommended by the property manager and president of the condo building. found their workmanship and attention to details very good and very thorough. were able to resolve small problems and situations and happy to feel the heat in my unit. it's pricey, but happy was done by a very professional service. thank you.

by alisiena from Toronto on Twintech Heating and Cooling

Fantastic team. Completed the job as per the specifications and in under 3 hours. Highly recommended Twintech.

by David from Toronto on Twintech Heating and Cooling

During the summer, I previously hired TwinTech to replace my air conditioner when it failed. They did an excellent job so when I decided to proactively replace the furnace I contacted them. The furnace I had was 22 years old and showed signs of internal leakage. It still worked but rather than wait to have it fail in cold weather, I decided to purchase a higher efficiency model before it failed and take advantage of energy efficiency rebates. TwinTech offered very useful advice on the make and model of furnace to choose including high efficiency and variable speed motor. The price was reasonable, TwinTech arrived at the allotted time, installed the new furnace (including some re-routing of exhaust lines since the existing ones were too close to other vents), removed the old furnace, tested the installation and cleaned everything up. Overall, it was a good experience, they did a great job and the new furnace is working well.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

Does a Furnace Reduce its Efficiency as it Ages?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 9, 2024

Yes, a furnace can experience a reduction in efficiency as it ages. Several factors contribute to this decline. Wear and Tear: Over time, the components of a furnace, such as the heat exchanger, blower motor, and igniter, can wear out or become

Read More

How Long Can My AC Run Before Breaking?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 28, 2024

The lifespan of an air conditioning (AC) unit and how long it can run continuously without breaking depends on several factors, including the type and quality of the unit, how well it is maintained, the conditions in which it operates, and usage patt

Read More

Common Mistakes When Getting a New Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 20, 2025

Here are some common mistakes people make when getting a new furnace, and how to avoid them: Choosing the Wrong Size A furnace that's too big will cycle on and off frequently, leading to uneven heating and higher energy bills. Too smal

Read More

Unusual Noises From Furnace

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - November 28, 2024

If you’re hearing unusual noises from your furnace, it could signal a problem that needs immediate attention. Here's a guide to some common noises and their potential causes: 1. Banging or Popping Cause: This often indicates delaye

Read More