The flashing LEDs on your furnace will correspond to a specific fault code that is shown here on their diagnostic chart.


Founded in 1874, YORK has been an industry leader since the beginning. A revolutionary YORK "air washing" system installed in 1914 was the precursor to modern-day air conditioning. In 1924, the world's first air-conditioned office building used YORK equipment. And today, YORK products are heating and cooling iconic structures, including the Empire State Building, the English Chunnel, the U.S. Capitol Building and the Sydney Opera House.


York Furnace error codes are seen in three colors, red, green, and amber/yellow. Each color will also flash a specific number of times to signify a specific error. Breaking down each color, and number of flashes, will help you solve the problem you are having with your York Furnace.


CODE: SLOW GREEN FLASH
RESULT: Normal operation

CODE: SLOW AMBER FLASH
RESULT: Normal operation with call for heat

CODE: RAPID RED FLASH
RESULT: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
RESULT: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
RESULT: The control is receiving a "Y" signal from the thermostat without a "G" signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
RESULT: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
RESULT: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
RESULT: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
RESULT: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
RESULT: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
RESULT: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a "Delay on" mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
RESULT: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
RESULT: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
RESULT: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
RESULT: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
RESULT: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
RESULT: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
RESULT: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
RESULT: This control includes a "watchdog" type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the "watchdog" would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
RESULT: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.


See What Our Customers Are Saying:

by LP from Pickering on Twintech Heating and Cooling

All interactions from sales to installation were Courteous and professional. The installation was seamless and the attention to detail including clean up was outstanding. I highly recommend TwinTech Heating and Cooling.

by David in Pickering on Twintech Heating and Cooling

Twintech's Salesman Dave arrived promptly was friendly and courteous, listened and assured us the installation would be completed according to our requests. The crew arrived early morning on May 11th, 2018 and worked through till late afternoon non-stop. They were very friendly, very professional, their expertise was excellent, their workmanship outstanding and the installation was completed in a timely and efficient manner. We were completely satisfied and happy with the quality of the work.

by Jennifer in Toronto on Twintech Heating and Cooling

I had cold and hot spots all over my 70 yr old home. My furnace is quite new and Greg optimized the fan and furnace. The original installer just took it out of the box with factory settings and installed it- basically running at 50% of capacity. Greg also routed heat into my laundry room, yeah - so now I can renovate laundry room - thanks Greg. He is honest, professional and knowledgeable. I will be calling him back in the spring to optimize my AC as well.

by Happy Homeowner in Toronto on Twintech Heating and Cooling

Wonderful from beginning to end. I tend to fret and worry about home improvements but the excellent team at TwinTech put my mind as ease. They listen, they are patient and best of all ... the work they did is amazing! I chose the Goodman 80K BTU 2 stage furnace and the matching Goodman air conditioner. Greg, Grant and Poitr "Peter" arrived on time, took great care, explained everything to me and they answered all of my questions. They carefully adjusted the factory settings to optimize the furnace for my house and they also checked the duct work in the basement. Dave, the Sales Manager, came by to say "hello" and to see if I was happy. YES, I am happy with the work! The furnace is very quiet. I have it running on low just to circulate the air in the house and it's so much quieter than my old furnace. When I need new duct work for an upcoming basement renovation TwinTech will be my first choice. I highly recommend TwinTech. PS. They were even nice to my dogs.

by Les G. from Pickering on Twintech Heating and Cooling

Greg was prompt on the scheduled day of installation and the work was done well within the time estimated beforehand. Installation was neat and the equipment and scope of work was as specified in the quote. One item I must point out is that we were faced with a "No Heat" situation the day before the scheduled installation and Greg came out to address it free of charge. Not only that, but he also corrected an installation fault with our smart thermostat that was not part of the original job, again free of charge.

by one19 in North york on Twintech Heating and Cooling

Greg came by to do a routine furnace checkup. He was very knowledgeable and professional, letting me know what's being checked/adjusted and giving me tips to ensure everything runs smooth. Very honest and upfront about what's working fine vs. what may need to be fixed/replaced. He didn't attempt to up sell anything that wasn't necessary. I'm glad to have finally found someone I can trust and rely on for all my HVAC needs - furnace, A/C, and hot water tank.

by Paul M. from Toronto on Twintech Heating and Cooling

I'm very happy with the work that was done. Everyone from salesperson to the installers were friendly and professional. They were on time and cleaned up the job site after it was installed. They also answered all my follow up questions promptly. I wouldn't hesitate to work with them or recommend them again.

by Kathy D.in Ajax on Twintech Heating and Cooling

Thanks to the team at Twin Tech for a great job installing my new heat pump/ac unit. The guys were very polite and professional. When they left you would never have known they had been there except for the new Mitsubishi unit on the wall!! would highly recommend the Twin Tech team.

by varga p. in Pickering on Twintech Heating and Cooling

Installed professionally, no delays, no rework needed. Very reliable contractor and sales person. Also installed BBQ gas line and some duct work.

by Private User on Twintech Heating and Cooling

Greg and Grant are friendly, reliable, and knowledgeable HVAC professionals. The twins, Dave and the entire team provided efficient top quality service. Our family plns to use Twintech for all of our future HVAC needs.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

Why Are My AC Energy Costs so High?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 4, 2024

There could be several reasons why your AC energy costs are high: Inefficient AC Unit: If your air conditioning unit is old or inefficient, it may be consuming more energy than necessary to cool your home. Consider upgrading to a newer, more

Read More

Switch to a Heat Pump This Summer

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 4, 2025

Summer’s heating up, and so is the demand for smarter, more efficient cooling solutions. If you're still relying on an outdated air conditioner or juggling multiple systems to stay comfortable, it's time to consider a better way.

Read More

Regular Furnace Maintenance: Keep Your Home Safe and Warm

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - September 8, 2024

The Importance of Regular Furnace Maintenance: Keep Your Home Safe and Warm As the colder months approach, ensuring that your furnace is functioning properly is crucial for keeping your home warm, comfortable, and safe. Regular furnace maintenance

Read More

Furnace Maintenance: Here’s What You Should Know

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 28, 2018

You might have certain furnace maintenance questions, especially since the heating season has just passed us. Remember, maintenance is key if you want your furnace to operate efficiently and reliably. It is never too early to prepare for the colder m

Read More