In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by gerard harrington from Ajax on Twintech Heating and Cooling

Greg and team were amazing! All interaction via email and text 100% professional. From consult to product recommendation their service was phenomenal!

Installed a Napoleon furnace (ecm dc drive variable 2-stage) and it was a game changer for the whole house. Blended air temperature through and through the entire house and it’s saving us money by cutting down our utility bill by ALOT!

by D &. from Whitby on Twintech Heating and Cooling

We purchased a new cooling & heating system from Twintech and the team was fantastic. From sales to installation, the team were great to work with. Friendly (our dog even enjoyed having them over), professional and accommodating. I’d recommend Twintech in a heart beat to anyone. Superb customer service.

by Anonymous from Pickering on Twintech Heating and Cooling

End to end service. From quote, overseeing installation, contacting and making arrangements for energy audit. Warranty program is comprehensive. Cleaned up mess of assistant walking through my place without proper indoor foot covering when I pointed out that I was not happy about footprints on my floors.

by Bob S in Pickering on Twintech Heating and Cooling

In April we hired Twintech Heating & Cooling to replace our 20 year old water tank & 35 year old air conditioner. We got 5 estimates for the job & decided to go with Twintech for the following reasons.

- The Sales Manager, Dave, was very personable & knowledgeable as all of our questions were answered. (We had a list of questions we asked each of the contractors when we got the estimates)
- We got 5 estimates for the job. All contractors verbally told us they had the required qualifications but Dave was the only one to physically show us their license & insurance documentation.
- Twintech carried the Napoleon air conditioner & we wanted to support Canadian industry as it is assembled in Barrie On.

Safety is important at Twintech as demonstrated when we discussed with Dave, the need to change our install date because of freezing rain. Access was required by navigating a set of outside steps & Dave identified that safety took precedence.
On the installation date, Greg, Peter & Grant showed up on time & methodically accomplished the removal & installation of both units. The guys did a great job cleaning up as well.

When the job was completed we mentioned to Greg that we were pleased with the work they had done & were going to have them come out & do our furnace inspection in Sept. Greg said we can save our money as he had inspected the heat exchanger on the furnace while doing the job & there was no need to have another inspection in Sept. We were very impressed with Greg’s initiative. This is top shelf service. Thank you Greg.

As the weather was too cool to complete a functional test of the air conditioner on the installation date, Dave made a follow-up call to us to see how things were going & Greg also came out to check the operation. No problems.

We are very happy we hired professionals like Dave, Greg, Grant & Peter & have no hesitation in recommending Twintech Heating & Cooling. They will now be our "go to" guys.

by ted diplock in Toronto on Twintech Heating and Cooling

These guys are the best. From start to finish they exceeded my expectations and delivered a great product. They accommodated the nuances of my 100 year old home which was really appreciated. The install was easy to schedule and done fantastically. I’m so excited to have an efficiently heated and cooled home.

by Private User from Kitchener on Twintech Heating and Cooling

Twintech were fast and efficient contractors. It only took 48 hours between an initial home visit and complete installation. The workmen were polite and hardworking. The site was left clean with the old furnace etc. removed. They helped arrange an environmental assessment in order that I could receive the maximum rebate. They even called me within a week to determine if I was satisfied with their work and to reassure me that I could call them anytime I experienced heating difficulties or had any questions. I recommend Twintech for your heating problems.

by dlcarroll in Vaughan on Twintech Heating and Cooling

Courteous and professional service from initial consultation through to the installation. We highly recommend Twintech for outstanding service in the industry. Competitive pricing, professional and accurate advice, attention to detail, respect for their client's home and cleaning up at the completion of installation.

by TraceyG from Toronto on Twintech Heating and Cooling

Last night was the coldest day of the year so far and I woke up to my house being 54 degrees... I called Twintech at 2:45am and Greg was on site by 3:30am. The furnace required a part and he returned to his shop and came back to my home around 4:15am, furnace up and running by 4:30am. THANK YOU TWINTECH! Your service is second to none.

by Cristelle from Ajax on Twintech Heating and Cooling

After much research & getting 4 quotes, we hired Twintech team for our new furnace installation, prices were fair, they carried great product brands & more importantly installation was expertly done by one of the owners (Greg & his assistant Peter) which gave me an added piece of mind. Dave was very organized & answered all my questions in great detail, especially re: the Enbridge & Govt. rebate program.

by David from Pickering on Twintech Heating and Cooling

My old air conditioner was 20 years old and developed a Freon leak and it was more cost effective to replace rather than repair. There are a large number of heating and air conditioning companies available in my area so I contacted several for quotes. Twintech heating and cooling responded quickly to the inquiry I left on their website and their sales person Dave came by the following day. He was knowledgeable about the field and was able to show copies of the various refrigeration and gas fitting licenses along with workmens compensation, TSSA and other certifications. He also suggested a particular manufacturer and model of AC unit appropriate to my house and gave me a quote. Since the price was reasonable, service had been good and the reviews on the internet were also good, I decided to purchase an AC unit from them. Installation was quickly scheduled. They showed up on time, did a good job installing the new unit including some sheet metal work to get the new heat exchanger to fit in the furnace duct, and cleaned up afterward. In addition, they noticed that my existing AC was installed too close to the furnace exhaust (based on building code) and were able to mount the new AC the appropriate distance from the exhaust. Overall, they did an excellent job and were a pleasure to work with.

See What Our Customers Are Saying:

by Aaron on Twintech Heating and Cooling

We are very happy to recommend this company to everyone. Our furnace broke down on Sunday morning. We phoned them and before noon Grant the owner showed up. He worked on the furnace for about a hour not wanting to give up to fix the problem. The furnace was 17 years old. I was the one talking about replacing it. End result was the next day it was all done. On the Sunday Bob came over with heaters to warm up the house. We decided to replace the water heater at the same time. Thanks Grant for the excellent work. Thumbs up.

by Linda on Twintech Heating and Cooling

Right on time. Explained how to work the HRV in a different way so the house would not be so dry. Changed my whole house water filter for me as well. Friendly, helpful, caring service!

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

How to Choose a Furnace?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - March 24, 2021

Is your furnace nearing its end of life If you answered yes, then it's time to start looking for a new one before it is too late.When looking into replacing your heating unit, there are a few things to keep in mind when purchasing a furnace. And the

Read More

Why Isn't My Heat Pump Defrosting?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - October 24, 2023

If your heat pump is not defrosting as it should, it can lead to reduced heating efficiency and potential damage to the system. There are several reasons why a heat pump might not be defrosting properly: Low Refrigerant: Low refrigerant leve

Read More

What Are Signs That My Furnace May Soon Require Replacement?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - December 10, 2019

At Twintech Heating & Cooling, repairing furnaces is our bread and butter! However, there comes a point in every furnace's life where even regular maintenance and the most skillful repairs can't save it. Here are some signs that your furnace migh

Read More

The Importance of Proper Furnace Installation

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - February 17, 2025

Proper furnace installation is essential for ensuring efficiency, safety, and long-term performance. Here’s why it matters: 1. Energy Efficiency A correctly installed furnace operates at peak efficiency, reducing energy waste and lowering

Read More