In some cases air conditioning system repair can be rather complicated for an average user. However, some of the typical problems are not that serious and don't require much more than basic skills. Even if you don't feel like troubleshooting your Rheem air conditioner on your own, you may use the check list below to gain a better understanding of the issue and not let a service company take advantage of you.


rheem A/C error codes

CODE: 0- Standby.
RESULT: No command for unit operation.
FIX: Normal operation.

CODE: c - First Stage Cooling.
RESULT: Unit has received a command for first stage cooling.
FIX: Normal operation.

CODE: c Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for first stage cooling during an active anti-short cycle timer or minimum run timer. Wait until unit timer has expired or press the TEST button to defeat short cycle delay..

CODE: C - Second Stage Cooling.
RESULT: Unit has received a command for second stage cooling.
FIX: Normal operation.

CODE: C Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage cooling during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: h - First Stage Heat Pump.
RESULT: Unit has received a command for first stage heat pump.
FIX: Normal operation.

CODE: h Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) action.
FIX: The unit has received a command for first stage heat pump during an active anti-short cycle timer or minimum run time. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: H - Second Stage Heat Pum.
RESULT: Unit has received a command for second stage heat pump.
FIX: Normal operation.

CODE: H Flashing.
RESULT: Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
FIX: The unit has received a command for second stage heat pump during an active anti-short cycle timer or minimum run timer. Wait unit timer has expired or press the TEST button to defeat short cycle delay.

CODE: d - Defrost Active.
RESULT: The unit is undergoing a defrost cycle.
FIX: Normal operation.

CODE: t - Test Mod.
RESULT: Test Mod.
FIX: The ICC is in TEST mode.

CODE: P - Protector Trip.
RESULT: A command for compressor operation is present but no current is measured to the compressor.
FIX: Motor protector open.

CODE: 01 - Long Run Time (Compressor).
RESULT: The compressor has continuously run for more than 18 hours in the cooling mode.
FIX: Low refrigerant charge. Air ducts have substantial leakage. Dirty indoor air filter. Dirty outdoor coil.

CODE: 02 - High Pressure.
RESULT: Compressor limit has opened four (4) times within a call for operation.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: 03 - Short Cycling.
RESULT: ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each .
FIX: Check thermostat wire connection. Check thermostat location in zone..

CODE: L4 - Locked Rotor.
RESULT: The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
FIX: Bad run capacitor. Low line voltage. Excessive refrigerant in compressor. Seized bearings in compressor.

CODE: 05 - Open circuit (Compressor Will not Run).
RESULT: The ICC has had a protector trip for longer than 4 hours.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity. Check for open compressor internal protector.

CODE: 06 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L6 - Compressor Open Start Circuit.
RESULT: The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 07 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: L7 - Compressor Open Run Circuit.
RESULT: The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
FIX: Check for damaged, miswired, or wrong run capacitor. Check for broken Wires, loose connectors, or miswired compressor. Check compressor windings for continuity.

CODE: 09 - Low Secondary Volts.
RESULT: The secondary voltage at R and C is below 18VAC.
FIX: Control transformer overloaded. Low line voltage.

CODE: 21 - Low Pressure Control Open.
RESULT: The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation .
FIX: Unit has low refrigerant charge. Indoor coil is frozen (cooling mode). Dirty indoor coil or filter (cooling mode). Indoor blower is not running (cooling mode). Outdoor coil is frozen (heating mode). Expansion valve is not operating correctly.

CODE: L21 Flashing.
RESULT: Active Protection, Low Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 21.

CODE: 27.
RESULT: Low Line Voltage or No Line Voltage Fault.
FIX: Check incoming line voltage to the disconnect and unit. Check wiring connections.

CODE: 28.
RESULT: High Line Voltage Fault.
FIX: Check line voltage.

CODE: 29.
RESULT: High Pressure Control Open. The ICC detects the HPC is open.
FIX: Outdoor coil is dirty (cooling mode). Outdoor fan is not running (cooling mode). Dirty indoor coil or filter (heating mode). Indoor blower is not running (heating mode). Liquid line restriction. Excessive refrigerant charge.

CODE: L29 Flashing - Active Protection.
RESULT: High Pressure Control Trip.
FIX: LPC has opened 3 times in the same cooling operation, the ICC has locked out the compressor to protect it. ICC alternately flashes L and 29.

CODE: 30 - Fuse Open.
RESULT: The ICC detects the on-board fuse is open.
FIX: The 3 amp fuse on the ICC is open. Low voltage Wiring at R and C is damaged or miswired.

CODE: 80 - Low Air Flow.
RESULT: The ICC detects that the indoor unit is not providing the minimum airflow requirements.
FIX: Misappliedwrong indoor air mover - replace With properly sized unit.

CODE: 83 - Condenser Coil Temperature Fault.
RESULT: The sensor detects an abnormally low or high coil temperature.
FIX: Replace the sensor. Check sensor is installed correctly on control.

CODE: 84 - Outdoor Ambient Temperature Fault.
RESULT: The sensor detects an abnormally low or high outdoor ambient temperature.
FIX: Check unit placement - If the outdoor unit is in a high temperature area, wait until the ambient temperature drops and check sensor reading. Replace the sensor. Check sensor is installed correctly on control.

CODE: 93 - Internal Control Fault.
RESULT: The control is not functioning properly.
FIX: Check control for proper system Operation. Replace control.

CODE: d1.
RESULT: N0 Shared Data.
FIX: Replace memory card With correct system information.

CODE: d3 - Airflow CFM Mismatch.
RESULT: The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
FIX: Misappliedwrong indoor air mover-replace With properly sized air handler/furnace.

CODE: d4 - (Device) Memory Card Invalid for Device.
RESULT: The data in the memory card inserted into the control board does not match the data in the control.
FIX: Check memory card to ensure it matches device. Check if memory card is present.

CODE: d8 - Old Shared Data.
RESULT: System data is obsolete.
FIX: If system Will not operate, order new memory card to update system information.


See What Our Customers Are Saying:

by Oldtown in Pickering on Twintech Heating and Cooling

Honest, very personable , men of their word ,workmanship xcellent ,showed up when promised ,They do not try to up sell ,rather give good advice instead . Price was very fair in my opinion .We have a family member with a medical condition and I think they made us a priority .Very happy with these guys . (Nice guys ) Stu Leffler Ajax.

by Mike B. Toronto on Twintech Heating and Cooling

Very professional, courteous, knowledgeable staff. Sales staff (David Gergley) excellent in knowledge and getting the job setup and installation was very prompt. Greg and Peter (technicians) knew their stuff and stuck around after completion to make sure it all worked properly and that I understood how it all was installed and how the unit worked. Would highly recommend them! Thanks for a great job-house is now cool and comfortable.

by Steve S in Toronto on Twintech Heating and Cooling

I had Twintech install a brand new air condition back in June of this year and I'm very happy with their service. I have a very busy schedule so I sent out an email to 7 or 8 HVAC companies just to get an idea of what it would cost. Dave at Twintech and only one other company were able to give me an approximate quote through email. Many of the companies I reached out to didn't even respond. I decided to meet with Dave and he was very friendly and professional. He gave me a good quote for a name brand/energy efficient AC with installation from their certified technicians. It was an easy decision to go with them.

Within a week I had the unit installed and working perfectly. Their technicians were very helpful and answered all of my questions. I'll definitely be calling them back for all of my HVAC needs in the future.

by Tina - Whitby in Whitby on Twintech Heating and Cooling

The people from Twintech were very friendly and personable...from the salesman to the installers. The installation was done as scheduled. I love my new air conditioner. My neighbour has a York and that thing is so noisy compared to my Goodman!! Thanks Twintech!!

by Cathy f. from Pickering on Twintech Heating and Cooling

Thank you, Twintech. They installed an A/C in my home in the middle of a heat wave which we appreciated very much. I found the team good, not overly friendly, other than the brothers. Dave, the salesperson was awesome, and, it's because of him that I was sold on using Twintech. I had other questions about additional work I am curious about and would have liked them to follow up and provide a quote. Other than that, which ultimately is not related to the great work they did, I would definitely recommend them, although I don't believe they go outside of Durham (check with them).

by Linda from Durham Region on Twintech Heating and Cooling

We have used this company a few times so I can't remember exactly what we paid but I do know that their fees are always very reasonable.

The first time we called Greg was when our furnace conked out while we were away. He came right away, showed me the problem and fixed it immediately.

The second time was when we needed an air conditioner moved and lifted to a platform. Again, he showed up on time, completed the job quickly (including a new gas line) and the fee was very reasonable.

We have received a quote from Greg to replace the air conditioner and furnace and when we are ready to move ahead, we will be calling him.

I have no hesitation in recommending TwinTech!

by AS from Pickering on Twintech Heating and Cooling

Our rating for Twintech is 5/5 stars. They are very professional and efficient, and the transparency they maintain right from the preliminary assessment till the day of the work is a testament to their experience in the field. We had Twintech replace our air conditioning and furnace, and we appreciate the efforts taken by Greg.

by Raymond from Toronto on Twintech Heating and Cooling

After 18 years my Air conditioner died in the middle of a heat wave. I entered my information on Home Stars and within the hour Dave from Twin Tech responded and offered to meet me as soon as possible depending on my availability. Dave was very knowledgeable about the products Twin Tech offered and even though this was the first quote I received . I felt very comfortable in giving Twin Tech my business. maybe it was the professional approach. Needless to say that the crew with Greg and Grant arrived promptly at the time they committed to were very professional and within a few hours had the place cool. They cleaned up and one would never know that I had work done . I know that the System is new and I probably wont need to worry about it for some time. However with the professionalism displayed by the crew I feel assured that should I need to call for service Twin Tech will respond. I also know that should I need a new Heating system I will go with Twin Tech. Keep up the good work.

by gerard harrington from Ajax on Twintech Heating and Cooling

Greg and team were amazing! All interaction via email and text 100% professional. From consult to product recommendation their service was phenomenal!

Installed a Napoleon furnace (ecm dc drive variable 2-stage) and it was a game changer for the whole house. Blended air temperature through and through the entire house and it’s saving us money by cutting down our utility bill by ALOT!

by D &. from Whitby on Twintech Heating and Cooling

We purchased a new cooling & heating system from Twintech and the team was fantastic. From sales to installation, the team were great to work with. Friendly (our dog even enjoyed having them over), professional and accommodating. I’d recommend Twintech in a heart beat to anyone. Superb customer service.

See What Our Customers Are Saying:

by Robert Rogers on Twintech Heating and Cooling

Very pleased with the professional service that TwinTech Heating and Cooling provided in replacing my furnace. I got several quotes from different service providers. Their price was excellent and they explained the features very well. We are very glad we went with TwinTech and highly recommend their services.

by Robert Mizuno on Twintech Heating and Cooling

We were new homeowners in need of a second opinion. TwinTech Heating & Cooling were Amazing and professional. Very knowledgeable and great service all around. Recommend to anyone looking for honest and reliable services. Treated with respect and care. Thank you Greg, Mitch and Bob!

by Ruth on Twintech Heating and Cooling

TwinTech is an excellent and honest company! I called them for a second opinion after being told by another company that I needed to replace my furnace. Turns out this was not the case at all! I did not need a new furnace. TwinTech did not push to make an unnecessary sale and saved me from a huge expense. Bob and Mitch were extremely professional and above all honest! I definitely recommend TwinTech!

by Anna Chin on Twintech Heating and Cooling

Amazing experience with TwinTech Heating & Cooling! Their team was professional, knowledgeable, and efficient from start to finish. They installed my new furnace quickly and left everything spotless. The technicians took the time to explain everything and made sure I was comfortable with the system before they left. Great customer service and fair pricing. I highly recommend them for anyone needing HVAC services!

by Connor Agnew on Twintech Heating and Cooling

Great experience all around. Bob was sharp and easy to talk to, and Greg handled the installation perfectly. Would hire them again in a heartbeat.

The Essential Guide to Air Conditioner Home Ownership

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - August 31, 2024

Owning an air conditioner is not just about enjoying cool, comfortable air during the sweltering summer months—it's about ensuring your unit runs efficiently, lasts longer, and provides value for your investment. Whether you're a new ho

Read More

How Does an AC Unit Normally Function?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - May 5, 2024

An air conditioning (AC) unit works by extracting heat from inside a building and transferring it outside, thereby cooling the indoor air. Here's a basic rundown of how a typical AC unit functions: Evaporation: The process begins with a

Read More

Are Portable ACs at all useful if you have no other options?

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - April 21, 2023

I have a friend who lives in an apartment that does not allow window units to be placed. Seems their only option is one of the portable ACs that stand on the floor that you just use the vent / exhaust hose going out the window. This would only

Read More

Most Common AC Error Codes

  • SUBMITTED BY:
  • TWINTECH HEATING & COOLING
  • - July 4, 2024

Air conditioners (AC) come with built-in error codes that help diagnose issues. Here's a list of some of the most common AC error codes and their meanings: General AC Error Codes E1: Indoor unit temperature sensor error E2: Indoor unit

Read More